background image

 
 
 
 
 

HRW HPE-BNSMA V401 Manual 111201.doc            E. & O. E. / Subject to change without notice 

Page 14 of 16 

Installation & Commissioning 

 

  This is an RS485 network device designed for mounting in an electrical panel. Ideally it should 

be mounted to the panel backplane in a horizontal position (RJ11 sockets on the lower side and 
communications ports on the upper side) 

 

  Each 24Vac power supply transformer should have the neutral (24Vac N) connection grounded 

at the electrical panel earth connection to ensure the device grounding is at the same potential 
as the network master’s grounding 

 

  Where more than one device is connected to a common transformer ensure that the 24Vac 

phasing is the same to each device (‘A’ connects to ‘A’, ‘N’ connects to ‘N’ in all cases) 

 

  If the red comms light adjacent to the RS485 terminals emits an obvious flash every time 24Vac 

power is applied to the device then the micro-processor may be corrupted. The micro processor 
should be replaced 

 

  RS485 multi-drop cable should be used for the network connections, complete with end of line 

terminating resistors (120

). Belden 9841 or equivalent is recommended. The recommended 

cable is a low capacitance twisted pair with braid and foil screen 

 

  The RS485 cables should be terminated directly at each device in a daisy-chain configuration, 

avoiding ‘laterals’ or ‘spurs’ 

 

  The RS485 screen should be connected at the network master’s ground terminal. The incoming 

and outgoing screen at each device should be continuously connected via the S terminal of the 
device (note that the device’s S terminal has no electrical connection to the device, it merely 
acts as a junction terminal for the purpose of screen continuity) 

 

  The RS485 cable should avoid cable routes that run with power cables. Where the RS485 

cable must cross power cables then they should cross at 90° avoiding parallel runs beside 
power cables  

 

  Prior to connection of the slave devices to the RS485 network check that no AC voltage is 

present. Double check the network for short circuits between the twisted pair cores and 
between the cores and the screen. Ensure continuity of the twisted pair cores and the screen 

 

  Check the network master’s +/- terminals for correct voltages to ground (approx. 2.5Vdc) and 

connect the RS485 network cable to the network master’s RS485 port  

 

  At each device assign an individual address and the baud rate specific to the network. Write the 

changes, eXit the terminal application and remove the HPECOM cable 

 

  Verify network voltage at the RS485 connector (b/- and ground) and connect to the 

device. Communication can be verified by flashing of the red comms LED adjacent the 3 
terminal RS485 connector). Frequency of comms LED flash is baud rate dependant. At higher 
baud rates the LED flash may not be obvious, the LED appearing to be continuously on 

 

  Where a network runs between buildings and zero earth potential difference between individual 

panel 24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to 
provide isolation of the sections of the network having differing earth potential 

Summary of Contents for HPE-BNSMA

Page 1: ...nnected to the gateway for read access of up to 250 SMA data points Typical Applications BACnet MS TP network integration of SMA devices such as Sunnyboy inverter Windyboy inverter Sensorbox Feature Summary SMA terminal mode for network initialisation SMA network device identification SMA device points identification SMA individual point configuration as BACnet object BACnet application services S...

Page 2: ...tings 5 BREAK IN TO TERMINAL MODE 5 BACNET CONFIGRATION COMMANDS 6 SMA POINT CONFIGURATION COMMANDS 7 SMA TERMINAL MODE 8 COMMAND SUMMARY 8 OPERATION 8 POINT PROGRAMMING 9 POINT STRUCTURE 9 POINT SCALING 10 DOWNLOAD TEXT FILE 11 ENABLE SMA PORT 11 SCAN SMA NETWORK 12 FIND FUNCTION 12 DIAGNOSTIC DISPLAY 13 SMA POINT ERROR RESPONSE 13 INSTALLATION COMMISSIONING 14 CONNECTIONS 15 DIMENSIONS 15 TECHNI...

Page 3: ... the gateway s Diagnostic and Terminal functions mean the available data points can be identified without the manufacturer s manual if need be For each required SMA data point the gateway data base point configuration consists of 1 SMA device address 2 Channel number of the point required to be read 3 Scaling Type selection for manipulation of the read raw data before passing to the BACnet side 4 ...

Page 4: ...e are recommended A USB port Serial comm port DB9 converter may be required for HPECOM if the PC being used does not include a Com 1 serial port The following settings reflect HyperTerminal Please contact us if you require assistance setting up Indigo HyperTerminal Settings For successful communication between HyperTerminal and the device initial Properties setup of HyperTerminal should be as per ...

Page 5: ...tion Saving HyperTerminal Settings For ease of connection it is recommended to save the HyperTerminal setup for each baud rate you may wish to use with an easily recognised configuration name For example HPECOM 48 4800 HPECOM 96 9600 HPECOM 19 2 19200 HPECOM 38 4 38400 HPECOM 57 6 57600 Break in to Terminal Mode When HyperTerminal is running and the HPECOM cable is connected to the device the init...

Page 6: ...800 Example 1001 38400 After changing comm speed it will be necessary to reconnect with HyperTerminal at the new comm speed to save write the change Set Maximum Master address MM 1 127 Highest Master device address on the network is registered Next address searching limited to MM address Set Sys Vendor ID SysVid SV 0 255 System vendor specific features may be available SV 0 applies generic BACnet ...

Page 7: ...ith new data base will delete an old existing data base as a matter of course Find SMA point detail F Point data structure is revealed from a specified starting point Refer to the description on page 12 Scroll page display P 1 10 Scroll to specific page if more data points are present than can be displayed on one screen Example P 2 The second page of database settings are displayed Priority Releas...

Page 8: ...xit Terminal Mode X Return to normal point data base mode Operation After entering HyperTerminal communication with TTTTTTTTTTT then enter T to go to SMA Terminal Enter H to display the Help text Enter GN to view the available network devices including their current network addresses their serial numbers and device type 2 2000860214 WR6KA 05 1 6830 SENS0500 3 2000860207 WR6KA 05 If the current net...

Page 9: ...ysis Point Programming After eXit from SMA Terminal you can begin to enter gateway data points Each point from 4 253 may be configured to read a data point value from any SMA device present on the SMA network On the BACnet side each point 4 253 represents a BACnet object AV4 AV253 Point Structure Gateway point configuration is in the following structure Point SMA Device Addr SMA Channel Scaling Po...

Page 10: ...s may be assigned to a point either as a part of the Point Programming string as outlined in the previous point programming section or individually after initial point configuration once the live data is seen and the scaling requirements are clear To scale an individual point as being divided by 10 then a Scale type value of 1 must be assigned to that point as referenced in the left hand column of...

Page 11: ...icate that the existing data base is being blanked and now Ready to receive data base text file While in the Ready state navigate to the text file path via the Transfer Send Text File dialogue After download of the text file the display will indicate a check between lines received and lines expected as set at the 10000 nnn line If the lines check is correct then the new data base is loaded otherwi...

Page 12: ...el 1 4 1 1 0 204 enter Example 2 If you wish to reveal the channel detail and activity of all channels of device 3 from Counter Input Instant channel 1 4 3 1 0 307 enter Once you have set up point 4 according your search criteria then enter F and the points from the starting Table Row will be sequentially displayed so you can identify live channel data relating to the installation To Exit the Find...

Page 13: ...nse including the gateway s recognition of required data point values Via the HyperTerminal menus Transfer Capture text option you can save this communication data for later analysis create a capture file press Enter to force a scan then stop the capture Open the resultant text file with Word to view a formatted record of the communication for analysis SMA Point Error Response When the SMA device ...

Page 14: ...n at each device should be continuously connected via the S terminal of the device note that the device s S terminal has no electrical connection to the device it merely acts as a junction terminal for the purpose of screen continuity The RS485 cable should avoid cable routes that run with power cables Where the RS485 cable must cross power cables then they should cross at 90 avoiding parallel run...

Page 15: ... Manual 111201 doc E O E Subject to change without notice Page 15 of 16 Connections Dimensions If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45 5mm ...

Page 16: ...ices for control panel mounting Standard package 40 units per carton Accessories HDA0002 DIN rail adapter brackets factory fitted HPECOMU Configuration cable USB RJ11 HPECOM Configuration cable DB9 RJ11 U232 P9 RS232 DB9 USB adapter cable Other HP_BN Series Devices HPC0662BN Universal Controller 12 Point BACnet MS TP 24Vac HPC8884BN Universal Controller 28 Point BACnet MS TP 24Vac HPD0440BNMR Netw...

Reviews: