44
HP SureStore E Disk Array XP512/XP48: Owner’s Guide
.
Table 8. 3-Phase 60 Hz Operation
Specification
60 Hz-V1
60 Hz-V2s
60 Hz-V3
Nominal rated voltage (vac)
200
208
230
Minimum operating voltage (vac) 184
191
212
Maximum operating voltage (vac) 212
220
244
Rated line current (arms)
15
14.7
13.2
Dropout carry-through time at
minimum line voltage (ms)
500
500
500
Table 9. 3-Phase 50 Hz Operation
50 Hz-V1 50 Hz-V2s 50 Hz-V3 50 Hz-V4 50 Hz-V5 50 Hz-V6 50 Hz-V7
Nominal rated voltage (vac) 200
220
230
240
380
400
415
Minimum operating voltage
(vac)
184 202 212 221 350 368 382
Maximum operating voltage
(vac)
212 233 244 254 403 424 440
Rated line current (arms)
15
13.8
13.2
12.6
9.9
9.6
9.5
Dropout carry-through time
at minimum line voltage
(ms)
500
500
500
500
500
500
500
Summary of Contents for StorageWorks XP48 - Disk Array
Page 1: ...HP SureStore E Disk Array XP512 HP SureStore E Disk Array XP48 H Owner s Guide ...
Page 19: ...19 2 THE HP SURESTORE E DISK ARRAY XP512 HARDWARE ...
Page 45: ...45 3 THE HP SURESTORE E DISK ARRAY XP48 HARDWARE ...
Page 76: ...76 HP SureStore E Disk Array XP512 XP48 Owner s Guide ...
Page 86: ...86 HP SureStore E Disk Array XP512 XP48 Owner s Guide VCCI EMC Statement Japan ...
Page 87: ...Regulatory Statements 87 BSMI EMC License Number and Statement Taiwan XP512 XP48 ...
Page 88: ...88 HP SureStore E Disk Array XP512 XP48 Owner s Guide Harmonics Conformance Japan ...
Page 94: ...94 HP SureStore E Disk Array XP512 XP48 Owner s Guide ...
Page 106: ...106 HP SureStore E Disk Array XP512 XP48 Owner s Guide ...
Page 116: ...116 HP SureStore E Disk Array XP512 XP48 Owner s Guide ...