by protecting, for example, against power source failures or accidentally tripped circuit breakers.
The server can receive AC input from two different AC power sources.
System AC Power Specifications
Power Cords
Table B-3
lists the various power cables available for use with a HP Integrity rx7620 server. Each
power cord is 15 feet (4.5 meters) in length with a IEC 60320-1 C19 female connector attached to
one end.
Table B-3 Power Cords
Where Used
Description
Part Number
International-Other
Stripped end, 240 volt
8120-6895
International-Europe
Male IEC309, 240 volt
8120-6897
China
Male GB-1002, 240 volts
8121-0070
North America/Japan
Male NEMA L6-20, 240 volt
8120-6903
System Power Specifications
Table B-4
lists the AC power requirements for an HP Integrity rx7620 server. These tables provide
information to help determine the amount of AC power needed for your computer room.
Table B-4 AC Power Specifications
Comments
Value
Requirements
200/208/220/230/240 (VAC rms)
Nominal input voltage
50 - 60 (Hz)
Frequency range (minimum -
maximum)
1
Number of phases
Per line cord
12 amps
Maximum input current
Per line cord
30 A peak for 15 ms
Maximum inrush current
At all loads of 50% - 100% of supply rating
At all loads 0f 25% - 50% of supply rating
>0.98
>0.95
Power factor correction
Per line cord
<3.0 (ma)
Ground leakage current (mA)
Comments
VA
Watts
Power Required (50 - 60 Hz)
See #1 below
3220
3156
Maximum Theoretical Power
12A @ 220 VAC, see note #2
2640
---
Marked Electrical Power
See note #3
2030
1989
Typical Maximum Power
110
System Specifications
Summary of Contents for rp7420
Page 3: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 30: ...Figure 1 12 Left Rear View of HP 9000 rp7420 server 30 Overview ...
Page 40: ...40 ...
Page 50: ...50 ...
Page 82: ...82 ...
Page 108: ...108 ...
Page 119: ...Figure D 3 Planning Grid Computer Room Layout Plan 119 ...
Page 120: ...Figure D 4 Planning Grid 120 Site Preparation Guidelines ...
Page 121: ...Figure D 5 Planning Grid Computer Room Layout Plan 121 ...
Page 122: ...Figure D 6 Planning Grid 122 Site Preparation Guidelines ...
Page 123: ...Figure D 7 Planning Grid Computer Room Layout Plan 123 ...
Page 124: ...124 ...
Page 127: ...X XD 115 127 ...