Specifications
This chapter provides the physical, input, and output specifications for the UPS. Topics
include battery descriptions, battery runtime estimates, and environmental requirements when
operating the UPS.
Physical Specifications
Table 6-1: Physical Specifications
Feature Metric
U.S.
Dimensions Width
44.45
cm
17.50
in
Height
44.45
cm
17.50
in
Depth
72.64
cm
28.60
in
Weight
189 kg
420 lb
Input Specifications
Table 6-2: Input Specifications
UPS Model
Utility
Voltage
Frequency
(Hz)
Default Settings—
Nominal Voltage (VAC)
Range
Available Settings—
Utility Voltage (VAC)
R12000 XR WW
(worldwide)
50/60
200-240
200, 208, 220, 230, or 240