Illustrated parts catalog 8
Electrical power component identification
Front view shown
Item
Component
Description
1
Demarcation box
1
Customer communication connection point for the following
components:
•
ECS
•
Access control
•
Phone
2
Fire box
1
Connection location for fire emergency and VESDAnet signals
3
480/415 transformer
cabinet
2
Converts main power from 480V to 415V for POD operation
4
380-415 VAC WYE,
3-phase, 320 A
Feed A and B power for IT critical loads busways and house power
1
The demarcation box and the fire box are communication data points that are provided on the POD by HP. Connecting
these data points is the responsibility of the customer, unless an approved Statement of Work is initiated.
2
This cabinet is designed for two transformers. The transformers are an optional component that might not be included.
Main breaker locations