Illustrated parts catalog 11
Item
Electrical safety label
Description
2
Do not enter label
Provides a warning to users not to enter while a fire is
extinguishing
4
Power disconnect label
States that power should be disconnected before maintenance
is performed
5
Short circuit current label
States that the design of the POD can withstand the available
fault current and describes the electrical system
6
Arc flash warning
Provides a reminder to users of the danger of arc flash and
required PPE
Internal panel labels
Front view shown
Item
Electrical safety label
Description
1
Power feeders caution label
Cautions users about phase rotation for all power feeders
2
Wire color code
Lists the 380-415 Y/200-240 V color codes:
•
Brown—Phase A/L1
•
Black—Phase B/L2
•
Grey—Phase 3/L3
•
Blue—Neutral
•
Green and yellow—Equipment ground
3
Panel schedule/circuit breaker
table/fuse list
Lists the layout and designation for all circuit breakers and lists
all fuse types and sizes