2.
Attach cage nuts
(H)
to the rear columns.
Item Reference
1 SEU
outline
2
Positions for mounting the cable management arm (refer
to step 8)
3
Positions for mounting the rear of the slides (refer to step
4)
4 Server
3.
Adjust the slides.
Item Measurements required for rack
1
465 mm (18.31 in)
Item Measurements required for rack
2
476.2 mm (18.75 in)
3
711 to 774.7 mm (28 to 30.5 in)
4.
Install the right and left slides into the rack. Do not
tighten the outer screws.
NOTE:
Single racks with a mounted component
exceeding 99.79 kg (220.99 lb) do not require a
stabilizer kit to be installed. However, when
extending a heavy unit for service, a kit is
recommended.
Single racks bolted to the floor or rack rows with
four or more bayed racks do not need a stabilizer kit
installed.