Chapter 2
System Specifications
Environmental Requirements
68
Environmental Requirements
This section provides the environmental, power dissipation, noise emission, and air flow specifications.
Temperature and Humidity Specifications
NOTE
The values in Table 2-14 meet or exceed all ASHRAE specifications.
Power Dissipation
Table 2-15 lists the power requirements by configuration (number of cell boards, amount of memory per cell,
and number of I/O chassis) for the HP Integrity Superdome/sx2000.
The table contains two columns of power numbers expressed in watts. The Breaker Power column lists the
power used to size the wall breaker at the installation site. The Typical Power column lists typical power.
Typical power numbers can be used to assess the average utility cost of cooling and electrical power.
Table 2-15 also lists the recommended breaker sizes for 4-wire and 5-wire sources.
Table 2-13
Operational Physical Environment Requirements
a
a. The maximum elevation for the operating environment is 3050 meters.
Temperature (dry bulb
ο
C)
b
b. Dry bulb temperature is the regular ambient temperature. Derate maximum dry bulb temperature
1°C/300 m above 900 m.
Relative Humidity %;
Noncondensing
Dew Point
c
c. Must be noncondensing environment.
Rate of Chg
(°C/hr, max)
Allowable
d,e
d. With installed media, the minimum temperature is 10°C and maximum relative humidity is
limited to 80%. Specific media requirements may vary.
e. Allowable: equipment design extremes as measured at the equipment inlet.
Recommended
f
f. Recommended: target facility design and operational range.
Allowable
e
Recommended
f
15 to 32
(59
ο
to 90
ο
F)
20 to 25
(68
ο
to 77
ο
F)
20 to 80
40 to 55
17
5
Table 2-14
Nonoperational Physical Environment Requirements
Storage
Powered Off (Installed)
Temp (°C, dry
bulb - regular
ambient temp.)
Rel Hum %;
Noncondensing
Dew point
(max)
Temp (°C, dry
bulb - regular
ambient temp.)
Rel Hum %;
Noncondensing
Dew point
(max)
-40 to 60
8 to 90
32
5 to 45
8 to 90
29
Summary of Contents for Integrity Superdome sx2000
Page 8: ...Contents 8 ...
Page 10: ...Tables 10 ...
Page 14: ...Figures 14 ...
Page 53: ...Chapter 1 Overview New Server Cabling 53 Figure 1 11 Backplane Cables ...
Page 169: ...Appendix A 169 A sx2000 LEDs ...
Page 174: ...Appendix A sx2000 LEDs 174 ...
Page 187: ...Appendix B Management Processor Commands MP Command HE 187 Example B 11 HE Command ...
Page 199: ...Appendix B Management Processor Commands MP Command PS 199 Example B 20 PS Command ...
Page 212: ...Appendix B Management Processor Commands MP Command XD 212 ...
Page 230: ...Appendix D Templates Templates 230 Figure D 2 SD16 and SD32 Space Requirements ...
Page 233: ...Appendix D Templates Templates 233 Figure D 4 Computer Floor Template ...
Page 234: ...Appendix D Templates Templates 234 Figure D 5 Computer Floor Template ...
Page 235: ...Appendix D Templates Templates 235 Figure D 6 Computer Floor Template ...
Page 236: ...Appendix D Templates Templates 236 Figure D 7 Computer Floor Template ...
Page 237: ...Appendix D Templates Templates 237 Figure D 8 Computer Floor Template ...
Page 244: ...Appendix D Templates Templates 244 ...
Page 247: ...Index 247 W wiring check 101 wrist strap usage 76 ...