Chapter 2
System Specifications
Electrical Specifications
66
WARNING
Beware of shock hazard. When connecting or removing input power wiring, always
connect the ground wire first and disconnect it last.
Component Power Requirements
Table 2-8 and Table 2-9 list the ac power requirements for an HP Integrity Superdome/sx2000 system. These
tables provide information to help determine the amount of ac power needed for the computer room.
I/O Expansion Cabinet Power Requirements
The I/O expansion cabinet (IOX) requires a single-phase 200-240V ac input. Table 2-10 lists the ac power
requirements for the I/O expansion cabinet.
NOTE
The IOX accommodates two ac inputs for redundancy.
Product label maximum current, 3-phase, 4-wire
44 A rms
Per phase at 200 to 240 V ac
Product label maximum current, 3-phase, 5-wire
24 A rms
Per phase at 200 to 240 V ac
Power factor correction
0.95 minimum
Ground leakage current (mA)
> 3.5 mA
See the following WARNING.
Table 2-9
Component Power Requirements (Without Support Management
Station)
Component
Component Power Required
50 Hz to 60 Hz
a
a. A number to use for planning, to allow for enough power to upgrade through
the life of the system.
Maximum configuration for SD16
8,200 VA
Maximum configuration for SD32
12,196 VA
Cell board
900 VA
I/O card cage
500 VA
Table 2-8
Power Requirements (Without Support Management Station)
Requirement
Value
Comments
Summary of Contents for Integrity Superdome sx2000
Page 8: ...Contents 8 ...
Page 10: ...Tables 10 ...
Page 14: ...Figures 14 ...
Page 53: ...Chapter 1 Overview New Server Cabling 53 Figure 1 11 Backplane Cables ...
Page 169: ...Appendix A 169 A sx2000 LEDs ...
Page 174: ...Appendix A sx2000 LEDs 174 ...
Page 187: ...Appendix B Management Processor Commands MP Command HE 187 Example B 11 HE Command ...
Page 199: ...Appendix B Management Processor Commands MP Command PS 199 Example B 20 PS Command ...
Page 212: ...Appendix B Management Processor Commands MP Command XD 212 ...
Page 230: ...Appendix D Templates Templates 230 Figure D 2 SD16 and SD32 Space Requirements ...
Page 233: ...Appendix D Templates Templates 233 Figure D 4 Computer Floor Template ...
Page 234: ...Appendix D Templates Templates 234 Figure D 5 Computer Floor Template ...
Page 235: ...Appendix D Templates Templates 235 Figure D 6 Computer Floor Template ...
Page 236: ...Appendix D Templates Templates 236 Figure D 7 Computer Floor Template ...
Page 237: ...Appendix D Templates Templates 237 Figure D 8 Computer Floor Template ...
Page 244: ...Appendix D Templates Templates 244 ...
Page 247: ...Index 247 W wiring check 101 wrist strap usage 76 ...