Removing and replacing the
Removing and replacing the HPE
HPE 800 W Flex Slot -48 VDC hot-plug power supply
800 W Flex Slot -48 VDC hot-plug power supply
The DC power supply option kits do not ship with a Power Supply DC cable Kit and may not include a Power Supply Cable Lug kit. The
optional DC Cable kit or the optional DC Cable Lug Kit may be purchased directly from Hewlett Packard Enterprise or an authorized
HPE reseller. For additional information, refer to the power supply QuickSpecs at https://www.hpe.com/info/fsps-qs
https://www.hpe.com/info/fsps-qs.
WARNING:
WARNING:
To reduce the risk of electric shock, fire, and damage to the equipment, you must install this
product in accordance with the following guidelines:
The HPE 800 W Flex Slot -48 VDC hot-plug power supply is intended only for installation in
Hewlett Packard Enterprise servers located in a restricted access location.
The HPE 800 W Flex Slot -48 VDC hot-plug power supply is not intended for direct
connection to the DC supply branch circuit. Only connect this power supply to a power
distribution unit (PDU) that provides an independent overcurrent-protected output for each
DC power supply. Each output overcurrent-protected device in the PDU must be suitable for
interrupting fault current available from the DC power source and must be rated no more
than 30 A.
The PDU output must have a shut-off switch or a circuit breaker to disconnect power for
each power supply. To completely remove power from the power supply, disconnect power
at the PDU. Disconnect the power for each power supply, if there are multiple power
supplies.
In accordance with applicable national requirements for Information Technology Equipment
and Telecommunications Equipment, this power supply only connects to DC power sources
that are classified as SELV or TNV. Generally, these requirements are based on the
International Standard for Information Technology Equipment, IEC 60950-1/IEC 62368-1. In
accordance with local and regional electric codes and regulations, the DC source must have
one pole (Neutral/Return) reliably connected to earth ground.
You must connect the power supply ground screw located on the front of the power supply
to a suitable ground (earth) terminal. In accordance with local and regional electric codes
and regulations, this terminal must be connected to a suitable building ground (earth)
terminal. Do not rely on the rack or cabinet chassis to provide adequate ground (earth)
continuity.
Prerequisites
Prerequisites
Components included with the hardware option kit are available
No. 1 Phillips screwdriver
Optional Q0H80A HPE 800W DC Power Cable Kit can be purchased from an HPE authorized reseller.
If you are not using an input power cord option, the power supply cabling must be made in consultation with a licensed electrician
and be compliant with local code.
If you are replacing the factory installed ground lug, use the KST RNB5-5 crimp terminal ring or equivalent. Use an M5-0.80 x 8
screw to attach the ground lug to the power supply.
Procedure
Procedure
1. Release the cable management arm .
2. If the server is using a single power supply only, remove all power from the server:
a. Back up all server data.
c. Disconnect all peripheral cables from the server.
3. Release the power cords from the strain relief straps.
4. To access the ground cable screw, slide the power supply out of the bay.
Removing and replacing the HPE 800 W Flex Slot -48 VDC hot-plug power supply
76
Summary of Contents for HPE ProLiant DL365 Gen10 Plus Server
Page 7: ...Illustrated parts catalog Illustrated parts catalog 7 ...
Page 18: ...Processor spare parts Processor spare parts 18 ...
Page 24: ...Network adapter spare parts Network adapter spare parts 24 ...
Page 43: ...Customer self repair 43 ...
Page 44: ...Customer self repair 44 ...
Page 45: ...Customer self repair 45 ...
Page 46: ...Customer self repair 46 ...
Page 47: ...Removal and replacement procedures Removal and replacement procedures 47 ...
Page 61: ...Removing and replacing the bezel Removing and replacing the bezel 61 ...
Page 67: ...7 Secure the cables Removing and replacing the ball bearing rails 67 ...
Page 104: ...provider Removing and replacing the system battery 104 ...
Page 124: ...Troubleshooting Troubleshooting 124 ...
Page 126: ...Diagnostic tools Diagnostic tools 126 ...
Page 138: ...Component identification Component identification 138 ...
Page 154: ...Device numbers 8 SFF device bay numbering 8 SFF 2 SFF device bay numbering Device numbers 154 ...
Page 155: ...Drives Drives 155 ...
Page 157: ...HPE Basic Drive LED definitions 157 ...
Page 160: ...Fan bay numbering Fan bay numbering 160 ...
Page 161: ...Cabling Cabling 161 ...
Page 179: ...Support and other resources Support and other resources 179 ...