2-40 HP Portable Chillers
Chapter 7: Appendix
57 of 78
Remote Condenser Assembly Models
To convert inches to
cm
, multiply dimension by
2.54.
Fan(s)
d
e
f
Remote Condenser
Refrigeration
g
Each
Totals
e
f
Overall Dimensions
Connections
Charge
HP Dia.
Motor
Amps
Air
flow
Net
wt.
Length Width Height
Mtg. Discharge Liquid
R-22
in.
hp
c
460V Fans cfm
h
lbs.
h
‘A’(in.) ‘B’(in) ‘C’(in.) ‘D’(in) ODS(in.) ODS(in.) lbs.
g
5
26
3/4 hp 1 ø
2.4
1
6,450 260
49.8
43.0
40.5
40.0
11
/
8
7
/
8
3.6
7.5
26
1
/
3 hp 3 ø
3.7
2
12,400 470
69.8
43.0
40.5
60.0
11
/
8
7
/
8
3.6
10
26
1
/
3 hp 3 ø
3.7
2
13,700 510
89.8
43.0
40.5
80.0
13
/
8
11
/
8
4.6
15
26
1
/
3 hp 3 ø
5.0
3
20,500 550
129.8
43.0
40.5
120.0
15
/
8
11
/
8
6.4
20
30 1 1/2 hp 3 ø
5.9
2
23,000 840
125.0
45.5
50.0
108.0
15
/
8
15
/
8
10.0
25
30 1 1/2 hp 3 ø
5.9
2
21,900 860
125.0
45.5
50.0
108.0
15
/
8
15
/
8
16.0
30
30 1 1/2 hp 3 ø
9.4
3
34,800 1,280
180.0
45.5
50.0
i
21
/
8
21
/
8
24.0
35
30 1 1/2 hp 3 ø
9.4
3
32,900 1,300
180.0
45.5
50.0
i
21
/
8
21
/
8
24.0
40
30 1 1/2 hp 3 ø 12.9
4
46,400 1,690
235.0
45.5
50.0
i
21
/
8
21
/
8
29.0
c
ø
represents electrical phase; all motors are 1,140 rpm. Multiply hp by
0.746
to convert to
kW
.
d
All first fan motors (Header Side) are ¾ hp (
0.56 kW
) single phase variable speed.
e
Multiply 460V amperages by
2.0
for 208-230V amperages.
f
Multiply 460 V amperages by
0.8
for 575 V amperages.
g
Refrigeration charge is for
remote condenser only!
h
To convert cfm to
cmh
, multiply by
1.699
. To convert lbs. to
Kg
, multiply by
0.454.
i
See drawing above.