Example 4 Programming of an alarm operating in a set interval with delay.
If we want that the alarm 1 will be switched on in the interval from 100 V to 300 V
and operate only after 10 seconds, one must:
enter into the programming mode, choose the
PrL
parameter of the alarm 1
and introduce the value 100
transit on the
PrH
parameter of the alarm 1 and introduce the value 300
transit on the
tYPA
parameter of the alarm 1 and select the function
On
transit on the
dLY
parameter of the alarm 1 and introduce the value 10.0
in case of the alarm state duration for a time longer than 10 seconds, the meter will
switch the alarm relay on
Example 5 Programming of an analog output
If we want to programme so that to the displayed value 0.00 mA will correspond
the value 4.00 on the analogue output, whereas to the value 20.00 mA , the value
20.00 mA, one must:
enter into the programming mode, choose the
IndO
parameter and switch the
individual characteristic
On
choose the
d_H1
parameter and introduce the value 0.00
transit on the
O_Y1
parameter and introduce the value 4.00
transit on the
d_H2
parameter and introduce the value 20.00
transit on the
O_Y2
parameter and introduce the value 20.00
Example 6 Bargraph programming
If we want to programme so that the bargraph was of a ,,sector” type - red colour
between PrL and PrH parameters, one must:
enter into the programming mode , choose the
tYPb
parameter of the
bargraph and choose
SEct
choose the
coLr
parameter of the bargraph 1 and choose
r
Example 7 Programming a bargraph with a ,,magnifier”
If we want to programme so that the bargraph was blank for the value 0 and full
lighted for the value 150, one must:
enter into the programming mode , choose the
brL
parameter of the bargraph
and introduce the value 0
choose the
brH
parameter of the bargraph 1 and introduce the value 150
Example 8 Programming of recording every 20 sec from 12:30