9. EXAMPLES OF NA5 METER PROGRAMMING
Example 1. Programming of the individual characteristic
.
If we want to programme so that to the value 4.00 mA will correspond the value 0
on the display, whereas the value 100, to the value 20.00 mA, one must:
enter into the programming mode and choose the
D_ P
parameter
responsible for the decimal point. Set the decimal point on
00000
choose the
Ind
parameter and switch the individual characteristic
On
choose the
I_H1
parameter and introduce the value 4.00
transit on the
d_Y1
parameter and introduce the value 0
transit on the
I_H2
parameter and introduce the value 20.00
transit on the
d_Y2
parameter and introduce the value 100
Example 2 Programming of an inverse individual characteristic
.
If we want to programme so that to the value 4.00 mA will correspond the value 120.5
on the display, and the value 10.8, to the value 20.00 mA, one must:
enter into the programming mode and choose the
D_P
parameter responsible
for the decimal point. Set the decimal point on
0000.0
choose the
Ind
parameter and switch the individual characteristic
On
choose the
I_H1
parameter and introduce the value 4.00
transit on the
d_Y1
parameter and introduce the value 120.5
transit on the
I_H2
parameter and introduce the value 20.00
transit on the
d_Y2
parameter and introduce the value 10.8
Example 3 Programming of the alarm with hysteresis
If we want to programme the alarm 1 operation so that at the value 850
C, this
alarm will be switched on, whereas it will be switched off at the value 100
C, and
the alarm 2 operation so that at the value 1000
C this alarm will be switched off
and switched on at the value -199
C, one must:
enter into the programming mode, choose the
PrL
parameter of the alarm 1
and introduce the value 100
transit on the
PrH
parameter of the alarm 1 and introduce the value 850
transit on the
tYPA
parameter of the alarm 1 and choose select the function
assigned as
nor
enter into the programming mode and choose the
PrL
parameter of the
alarm 2 and introduce the value 1000
transit on the
PrH
parameter of the alarm 2 and introduce the value -199
transit on the
tYPA
parameter of the alarm 2 and select the function
nor