Programmable parameters of NA5 meter
Table 1
Range of changes
Kind of input
Input parameter
Reesistance thermometers:
pt1
- Pt100
pt5
- Pt500
pt10
- Pt1000
Thermocouples:
te-j
- thermocouple, type J
te-h
- thermocouple, type K
te-n
- thermocouple, type N
te-e
- thermocouple, type E
te-r
- thermocouple, type R
te-s
- thermocouple, type S
te-t
- thermocouple, type T
re2
- resistance to 10 k
napl
- voltage to
300 mV
napH
- voltage to
600 V
nnal
- current to
40 mA
nnaH
- current to
5 A
Symbol
on the
display
Parameter description
Mathematical functions
0ff
typ
func
Chn
lo:n
Hi:n
Lower value of the input range
The setting of parameters LoIn
and HiIn gives the possibility to
narrow the measuring range down.
Setting possibility:
-1999... 9999
At the input signal < LoIn the meter dis-
plays the lower exceeding. The condition
Loln<Hiln must be fulfilled. The parame-
ter does not take into consideration the
individual characteristic, is operates on
the measuring signal.
Upper value of the input range.
Setting possibility:
-1999... 9999
At the input signal > HiIn the meter dis-
plays the upper exceeding. The condition
Loln<Hiln must be fulfilled. The parame-
ter does not take into consideration the
individual characteristic, is operates on
the measuring signal.
s)r
- raising to a power (result)
2
s)rt
- extraction of roots
result
- mathematical functions
switched off;