Hoymiles HME-1000T-AU User Manual Download Page 15

                                                                                         

 

©  2019  Hoymiles  Converter  Technology  Co.,  Ltd.  All  rights  reserved.

                                            15   

 

HME-1000T/1200T/1350T/1500T-AU 

 

126 

Software error code 

126 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support. 

127 

Firmware error 

1.Check if the firmware is correct and upgrade again. 

2.Check  the  communication  between  DTU  and  Hoymiles  monitoring 

system,  the  communication  between  DTU  and  microinverter.  Then  try 

again. 

3.  If  the  fault  still  exists,  contact  your  dealer  or  Hoymiles  technical 

support. 

128 

Software error code 

128

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

129 

Software error code 

129

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

130 

Offline

 

1.Please make sure that the microinverter works normally. 

2.Check  the  communication  status  between  the  DTU  and  hoymiles 

monitoring  system  or  between  the  DTU  and  the  microinverter.If  the 

communication is poor, try to make some improvements. 

3. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

141 

Grid overvoltage

 

1.  If  the  alarm  occurs  accidentally,  the  grid  voltage  may  be  abnormal 

temporarily.  The  microinverter  can  recover  automatically  after  grid 

voltage becomes normal. 

2. If the alarm occurs frequently, check whether the grid voltage is within 

the acceptable range. If no, contact the local power operator or change 

the grid overvoltage protection limit via Hoymiles monitoring system with 

the consent of the local power operator.

 

142 

10 min value grid 

overvoltage

 

1.  If  the  alarm  occurs  accidentally,  the  grid  voltage  may  be  abnormal 

temporarily.  The  microinverter  can  recover  automatically  after  grid 

voltage becomes normal. 

2. If the alarm occurs frequently, check whether the grid voltage is within 

the acceptable range. If no, contact the local power operator or change 

the grid overvoltage protection limit via Hoymiles monitoring system with 

the consent of the local power operator.

 

143 

Grid undervoltage

 

1.  If  the  alarm  occurs  accidentally,  the  grid  voltage  may  be  abnormal 

temporarily.  The  microinverter  can  recover  automatically  after  grid 

voltage becomes normal. 

2. If the alarm occurs frequently, check whether the grid voltage is within 

the acceptable range. If no, contact the local power operator or change 

the  grid  undervoltage  protection  limit  via  Hoymiles  monitoring  system 

Summary of Contents for HME-1000T-AU

Page 1: ...Version 1 2 June 2020...

Page 2: ...control the production of a single photovoltaic module directly consequently improving the flexibility and reliability of the system About the Manual This manual contains important instructions for t...

Page 3: ...hlights 8 3 3 Terminals Introduction 8 3 4 Dimension mm 8 4 About Function 9 4 1 Work Mode 9 5 About Installation 9 5 1 Accessories 9 5 2 Installation Precaution 10 5 3 Space Distance Required 10 5 4...

Page 4: ...ification 22 8 2 Power Quality Response Modes 22 8 3 DRM 22 9 Technical Data 23 8 1 DC Input 23 8 2 AC Output 23 8 3 Efficiency Safety and Protection 24 8 4 Mechanical Data 24 8 5 Features 24 Appendix...

Page 5: ...below 2 About Safety 2 1 Important Safety Instructions The HME 1000T 1200T 1350T 1500T AU Microinverter is designed and tested according to international safety requirements However certain safety pr...

Page 6: ...onal protective equipment including gloves and eye protection during the installation Inform the manufacturer about non standard installation conditions Do not use the equipment if any operating anoma...

Page 7: ...at the interference will not occur in a particular installation To confirm that the radio or television reception is interfered by this equipment you can turn the equipment off and on If this equipmen...

Page 8: ...efficiency 96 70 CEC weighted efficiency 96 50 Static MPPT efficiency 99 80 Dynamic MPPT efficiency 99 76 in overcast weather Power factor adjustable 0 8 leading 0 8 lagging External antenna for stron...

Page 9: ...Grid Stand by There are several circumstance that Microinverter will stay in Standby mode The current condition is contradicted with Microinverter operating requirement No house loads or the Export co...

Page 10: ...sure to ensure ventilation and heat dissipation Note For some countries the DTU will be required to meet the local grid regulation e g G98 99 for UK etc 5 3 Space Distance Required If the microinverte...

Page 11: ...rating due to an increase in the microinverter internal temperature do not expose it to direct sunlight To avoid overheating always make sure the air flow around the inverter is not blocked Do not in...

Page 12: ...se install the microinverter at least 50cm above the ground roof for better communication with Hoymiles DTU Step 2 Complete the AC Connection A Attach the AC bus cable with the mounting rail and fix t...

Page 13: ...slot accordingly Tighten the screws and then tighten the cap back to the port Plug the upper cover back to the bus connector B Connect the other side of the AC end cable to the distribution box and w...

Page 14: ...install the DTU and set up the monitoring system Product information is subject to change without notice Please download reference manuals at www hoymiles com 6 Troubleshooting 6 1 Troubleshooting Li...

Page 15: ...ween the DTU and the microinverter If the communication is poor try to make some improvements 3 If the alarm occurs frequently and cannot be recovered contact your dealer or Hoymiles technical support...

Page 16: ...rid frequency change rate is within the acceptable range If no contact the local power operator or change the grid frequency change rate limit via Hoymiles monitoring system with the consent of the lo...

Page 17: ...correct 301 Hardware Error Code 301 1 If the alarm occurs accidentally and the microinverter can still work normally no special treatment is required 2 If the alarm occurs frequently and cannot be re...

Page 18: ...Flashing green five times 0 3s gap Start up success Flashing Red five times 0 3s gap Start up failure 2 Run Process Flashing Fast Green 1s gap Producing power Flashing Slow Green 2s gap Producing powe...

Page 19: ...lease return it to the factory for replacement 6 4 Routine Maintenance 1 Only authorized personnel are allowed to carry out the maintenance operations and are responsible to report any anomalies 2 Alw...

Page 20: ...unit 6 5 Replace Microinverter a How to remove the Microinverter De energize the AC branch circuit breaker Remove the PV panel from the racking and cover the panel Using a meter to measure and make s...

Page 21: ...particular the electronic components from violent shocks humidity vibration etc Please dispose the packaging elements in appropriate ways to avoid unforeseen injury It is the customer s responsibilit...

Page 22: ...ting the PV System to Hoymiles monitoring app portal For details of how to configure monitoring please refer to document HMP Operating Guide Webpage V2 0 and HMP Operation Guide APP 8 2 Power Quality...

Page 23: ...rter Refer to Hoymiles Warranty Terms Conditions for more information 8 1 DC Input 8 2 AC Output Model HME 1000T AU HME 1200T AU HME 1350T AU HME 1500T AU Commonly used module power W Up to 310 single...

Page 24: ...verter efficiency 96 70 96 70 96 70 96 70 CEC weighted efficiency 96 50 96 50 96 50 96 50 Nominal MPPT efficiency 99 80 99 80 99 80 99 80 Night time power consumption mW 50 50 50 50 Model HME 1000T AU...

Page 25: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 25 HME 1000T 1200T 1350T 1500T AU...

Page 26: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 26 HME 1000T 1200T 1350T 1500T AU Appendix 1 Installation Map...

Page 27: ...RING DIAGRAM 230VAC SINGLE PHASE GROUND NEUTRAL W AC DISTRIBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREEN G L1 PHASE L1 ETHERNET CONNECTION TO BROADBAND ROUTER CONNECTION T...

Page 28: ...IBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREEN G L1 L2 L3 ETHERNET CONNECTION TO BROADBAND ROUTER CONNECTION TO DTU POWER ADAPATER 5V DTU UP TO 24 HME 1500T AUs PHASE L1 P...

Reviews: