Overload Condition
An Overload Condition begins when the
Overload Sensing Coil reads amperage from the
motor lead passing through it that is higher
than the Motor Overload Setting.
During an Overload Condition no voltage is
present at Ice Flaker Run Switch Leg (Term 6),
the Solenoid Valve Contacts (Term 7 & 8) are
open, and the Overcurrent Condition Indicator
Light is lit red.
The Motor Overload setting should be adjusted
on start-up and anytime changes are made to
the Drive Motor or Main Shaft.
Motor Overload Setting
The proper adjustment of Motor Overload
Setting will protect the Ice Flaker and help avoid
nuisance service calls.
To set the Motor Overload correctly,
1.
Mark the location of the setscrew
before an adjustment is made, as a
point of reference.
2.
Place a small flat blade screwdriver in
the adjustment screw while the Ice
Flaker is operating.
3.
Gently and slowly turn
counterclockwise until Overload
Condition Indication Light illuminates.
Do not force adjustment screw past
bottom stop.
4.
Then turn adjustment screw clockwise 1
hash mark and stop.
5.
Press the reset button to start the Ice
Flaker again.
Summary of Contents for HoweIce Rapid Freeze 4000-RL-CO 2DX
Page 6: ...6 Engineering Guidelines Figure 1...
Page 37: ...Appendix 37 Appendix Cut View 1000 RLE...
Page 38: ...38 Appendix Cut View 2000 RLE...
Page 39: ...Appendix 39 Assembly Drawing 1000 RLE Ice Flaker CP750 Mobile Express Ice Bin...
Page 40: ...40 Appendix Assembly Drawing 2000 RLE Ice Flaker CP1500 Mobile Express Ice Bin...
Page 41: ...Appendix 41 Wiring Diagram Ice Flaker Main Control Panel...
Page 42: ...42 Appendix Wiring Diagram CO2 EEV EEPR Control Panel...