1
Return heating
■
2
Flow heating
■
3
Return cooling
■
4
Flow cooling
■
5
Condensate connection
■
6
Access panel
Fig. 16: TopVent
®
MHC dimensional drawing
Unit size
MHC-6
MHC-9
MHC-9
Coil type
AC BC CC AC BC CC AD BD CD
A
mm
900
1100
1100
F
mm
758
882
882
G
mm
936
951
951
H
mm
858
873
873
I
mm
760
935
935
K
mm
1550
1622
1622
L
mm
594
846
846
O × P
mm
420 × 850
500 × 1050
500 × 1050
R
mm
2374
2496
2496
T
mm
1069
1104
1104
U
mm
1020
1220
1220
V
mm
1184
1235
1244
W
mm
1106
1157
1149
N
"
Rp 1¼ (internal)
Rp 1½ (internal)
Rp 1½ (internal)
J
"
Rp 1¼ (internal)
Rp 1½ (internal)
Rp 2 (internal)
M
"
G 1 (external)
G 1 (external)
G 1 (external)
Water content of heating coil
l
4.6
4.6
7.9
7.4
7.4 12.4
7.4
7.4 12.4
Water content of cooling coil
l
7.9
7.9
7.9 12.4 12.4 12.4 19.2 19.2 19.2
Weight
kg
295 299 305 377 377 388 388 388 399