6.4 Heat output
TopVent
®
TH, TC, THC recirculation units
Unit size
Coil type
Heat performance
P
rated,h
(in kW)
6
A
13.2
B
18.9
C
29.8
9
A
22.6
B
28.5
C
46.2
D
54.2
Reference:
Standard rating conditions for fan coil units
according to Commission Regulation (EU)
2016/2281
■
Room air temperature ..................20 °C
■
Extract air temperature ................22 °C
■
Fan ..............................................speed 2
■
Heating medium temperature.......45/40 °C
Table 7: TopVent
®
TH, TC, THC heat output
TopVent
®
MH, MC, MHC supply air units
Unit size
Coil type
Heat performance
P
rated,h
(in kW)
6
A
13.2
B
18.9
C
29.8
9
A
22.6
B
28.5
C
46.2
D
54.2
Reference:
Standard rating conditions for fan coil units
according to Commission Regulation (EU)
2016/2281
■
Room air temperature ..................20 °C
■
Extract air temperature ................22 °C
■
Fresh air temperature ..................12 °C
■
Fresh air ratio ..............................10%
■
Fan ..............................................speed 2
■
Heating medium temperature.......45/40 °C
Table 8: TopVent
®
MH, MC, MHC heat output
6.5 Cooling capacity
TopVent
®
TC, THC recirculation units
Unit size
Coil
type
Cooling capacity
(sensible)
(P
rated,c
) (in kW)
Cooling capacity
(latent)
(P
rated,c
) (in kW)
6
C
26.5
5.6
9
C
41.0
7.3
D
48.6
15.2
Reference: Standard rating conditions for fan coil units according to
Commission Regulation (EU) 2016/2281
■
Room air temperature ..................
27 °C (dry bulb)
19 °C (wet bulb)
■
Room air humidity ........................46.26 % rH
■
Extract air temperature ................29 °C
■
Fan ..............................................speed 2
■
Cooling medium temperature .......7/12 °C
Table 9: TopVent
®
TC, THC cooling capacity
TopVent
®
MC, MHC supply air units
Unit size
Coil
type
Cooling capacity
(sensible)
(P
rated,c
) (in kW)
Cooling capacity
(latent)
(P
rated,c
) (in kW)
6
C
26.5
5.6
9
C
41.0
7.3
D
48.6
15.2
Reference: Standard rating conditions for fan coil units according to
Commission Regulation (EU) 2016/2281
■
Room air temperature ..................
27 °C (dry bulb)
19 °C (wet bulb)
■
Room air humidity ........................46.26 % rH
■
Extract air temperature ................29 °C
■
Fresh air temperature ..................32 °C
■
Fan ..............................................speed 2
■
Cooling medium temperature .......7/12 °C
Table 10: TopVent
®
MC, MHC cooling capacity
12
13
TopVent
®
TH | TC | THC | MH | MC | MHC
Operating instructions
Technical data
Technical data
4 218 828-en-01
Summary of Contents for TopVent MC-6-C