8.3 Requirements for the installation site
■
Comply with the minimum and maximum distances.
■
Only secure the unit to ceilings or walls with sufficient load-bearing capacity.
■
Only secure the unit to ceilings or walls made of fireproof materials. The surface
temperature of the flue gas pipes amounts to 200°C. Please observe the
regulations of the responsible fire protection authorities.
■
Position the unit in such a way that no one is endangered by flue gas and
radiant heat and no fires can break out.
■
All air inlet and air outlet openings must be freely accessible. The supply air jet
must be free to spread out unhindered.
■
The access panels in the unit must be freely accessible.
■
The unit must be accessible for maintenance work. The connecting lines must
be able to be dismantled.
■
Make sure that supply air units draw in fresh air via the fresh air duct.
TopVent
®
TG / MG
X/2
X
Z
Y
1
■
1
Clearance of approx. 1.5 m for maintenance work
Size
6
9
Unit clearance X
min.
m
12.0
14.0
max.
m
23.0
31.0
Distance from ceiling Z
min.
m
0.3
0.4
Mounting height Y
min.
m
4.0
5.0
max.
m
approx. 9…25
1)
1) The maximum mounting height varies depending on the boundary conditions (for values,
see table of heat outputs or calculation with the 'HK-Select' selection program).
Table 19: TopVent
®
TG / MG minimum and maximum distances
20
21
TopVent
®
TG | GV | MG
Operating instructions
Transport and installation
Transport and installation
4 220 656-en-03