6 Technical data
6.1 Application limits
TopVent
®
TG, MG
Extract air temperature
max.
°C
50
Fresh air temperature (TopVent
®
MG)
min.
°C
– 15
Supply air temperature
max.
°C
55
Protection rating
IP 50
The units cannot be used in:
■
Damp locations
■
Places with a corrosive or aggressive environment
■
Spaces with a large amount of dust
■
Areas where there is danger of explosion
Table 6: TopVent
®
TG, MG application limits
TopVent
®
GV
Extract air temperature
max.
°C
50
Supply air temperature
max.
°C
55
The units cannot be used in:
■
Damp locations
■
Places with a corrosive or aggressive environment
■
Spaces with a large amount of dust
■
Areas where there is danger of explosion
Table 7: TopVent
®
GV application limits
6.2 Electrical connection
Unit type
TG-6
MG-6
TG-9
MG-9
GV-3
GV-5
Supply voltage
V AC
3 x 400
3 x 400
230
230
Permitted voltage tolerance
%
± 5
± 5 +10 / -15 +10 / -15
Frequency
Hz
50
50
50
50
Power consumption max.
W
1360
1960
300
750
Current consumption max.
A
2.3
3.4
1.4
3.5
Series fuse
A
13
13
16
16
Protection rating of unit control box
–
IP 56
IP 56
IP 00B
IP 00B
Table 8: Electrical connection
6.3
Air flow rate, gas consumption
Unit type
TG-6
MG-6
TG-9
MG-9
GV-3
GV-5
Nominal air flow rate
1)
m³/h
6000
9000
4200
8500
Minimum air flow rate
m³/h
4500
7000
2900
6000
Floor area covered
m²
537
946
140
290
Nominal heat input
max.
kW
32.0
66.0
32.0
55.0
Nominal heat output
max.
kW
28.9
61.2
28.9
50.7
Gas consumption
Natural gas: G20, G27 (H, E, Lw)
m³/h
3.4
7.0
3.4
5.8
Natural gas: G25, G25.3 (L, LL, K)
m³/h
3.8
7.9
3.8
6.6
1) at an air temperature of 20 °C
Table 9: Technical data
12
TopVent
®
TG | GV | MG
Operating instructions
Technical data
4 220 656-en-03
4 220 656-en-03