9.2 Maintenance
Maintenance schedule
Activity
Procedure
Interval
Clean unit
■
Clean inside of RoofVent
®
unit with vacuum cleaner.
■
Clean the heat exchanger and burner of the gas condensing boiler.
■
Remove the siphon, clean it and rinse the condensate drain.
1
×
annually
Functional check
■
Check function of the fan and actuators.
■
Check function of the Air-Injector.
■
Check the connections of the gas condensing boiler for leaks.
■
Check ignition electrode and readjust or replace if necessary.
■
Check function of the control system.
1
×
annually
Flue gas path test
■
Check flue gas pipe and, if required, clean inside.
1
×
annually
Emission measurement
■
Check setting of the gas control valve and readjust where necessary.
1
×
annually
Neutraliser
■
Loosen contaminated granulate and clean neutralisation unit with water.
Replace heavily soiled granulate.
1
×
annually
Check of the heat transfer fluid
■
Check the system pressure and top up with heat transfer fluid if necessary.
■
Take sample and test:
–
Test pH value with indicator strips
–
Test frost protection with a refractometer
1
×
annually
Filter change
■
Renew air filter.
Filter
Mat. No.
Quantity
Fresh air
2076260
2076262
2
1
Extract air
2078502
2076263
1
1
When the filter alarm is
displayed, at least 1
×
annually
Test of the inhibitor protection
■
Take a sample of the heat transfer fluid and have the inhibitor protection
analysed by a suitable service provider.
Every 3 years
Table 18: Maintenance schedule