Assembling the below-roof unit
The below-roof unit must only be assembled at the building site if it must be
delivered in multiple parts due to the unit version. Proceed as follows:
■
Make sure that the correct unit components match up (observe the unit number
and RoofVent
®
serial number).
■
Screw in the transport eyes into the connection module frame and attach the
lifting gear.
■
Lift the connection module complete with mounted components and rotate it
into the correct position.
Notice
Never change the orientation of the supply air silencer (option) relating
to the component above it. The correct position is marked on the unit.
■
Place the connection module on the bottom part.
■
Screw the components together; use the supplied screws and protective plugs
to do so.
1
2
3
4
■
1
Connection module
■
2
Heating section
■
3
Supply air silencer (option)
■
4
Air-Injector
Fig. 11:
Components of the below-roof unit
2
1
3
■
1
Unit number
■
2
Type plate with serial number
(behind the access door)
■
3
Serial number
Fig. 12:
Identification of the unit components
8x
Fig. 13: Transport eye in
the connection module
Fig. 14:
Below-roof unit screw connection with M6 x 20 screws and protective plugs
(8 per component)
Fig. 15: Correct orientation of the supply air silencer: Sound attenuation splitters parallel to the extract air grille
24
RoofVent
®
KG
Operating instructions
Transport and installation
4 220 755-en-00