4 214 864 / 02
ASSEMbly
2.2
Mounting the condensate drain
The consensate drain is to be mounted according to
!
CAUTION
To achieve a siphon effect, the condensate
drain hose must be routed as shown in the
drawing - fill the hose with water before com
-
missioning!
Fig. 03
Fig. 04
7.
For types 1800, 2200, 2800, 3500, 4200:
Remount support for door positioning (5, Fig. 01) on
the other side, readjust if necessary resp. level boiler
door first!
After changing over the hinges it might be necessary to
align (level) the boiler door! (Hanging boiler door)
Procedure:
8. Open boiler door approx. 10 cm.
9.
Raise boiler door (20-30 mm) by means of a mechan-
ical jack
(or jack) by slightly loosening flange nuts
(8, Fig. 02).
NOTICE
Do not loosen flange nuts entirely nor remove
them as the boiler door might fall down.
10.
After leveling the boiler door, retighten flange nuts
(8, Fig. 02) securely.
2.3
Installation of the thermal insulation
CAUTION
Cutting injuries as a result of sharp edges.
• Handle sections of the cladding carefully
and avoid contact with sharp edges.
1. Wrap the insulating mats (1.1/1.2, Fig. 06) around the
boiler body.
- Place the insulating mat (1.2) so that the black side
is on the outside and the large notch (1.2a) is on
the back.
2. Fit tension springs (2) to hold the ends of the insulat-
ing mats (1.1/1.2) together.
3. Fasten plastic straps (3) and strap fasteners (4).
- Do not overtighten the straps (reduced insulating
value).
4. Place insulating mats (5.1/5.2) against the rear wall
of the boiler and fasten them to each other and to the
insulating mat (1.2) with tension springs.
5.
Wrap insulating mat (6) around the flue gas collector
ring and secure with retaining disks (Fig. 05).
Fig. 05
6.
Wrap the insulating mat (7) around the flue gas col
-
lector and fix with retaining disks (Fig. 05).
7.
Place insulating mat (8.1/8.2/8.3) on the boiler front
and secure with the retaining discs (Fig. 05).
To facilitate attachment, the insulating mats
(8.1/8.2) can be cut through at the narrowest
point.
8. CompactGas (1800-4200):
Attach the insulating mat (9) to the boiler door without
retaining disks.
The following insulating mats are not at-
tached until the cladding is installed (see
- Insulating mats to prevent vertical air circu-
lation
- Insulating mats between the door and door
cladding