15. Photovoltaic heat pump
PV HP
52 °C
•
5 °C – T max: Target temperature range
when PV function activated.
This parameter determines the target
HW temperature to be reached solely
by the HP when the PV function is
activated.
16. Photovoltaic and electrical additional
heating (electric heating element)
PV EL
53 °C
•
5 °C – T max: target temperature range
when PV function activated.
This parameter determines the target
HW temperature to be reached solely
by the electrical additional heating when
the PV function is activated.
17. Holiday absence function
Holiday
OFF
•
«OFF»
«1 week»
«2 weeks»
«3 weeks»
«3 days»
«Manual» (see also point 18)
Deactivation/activation of the absence
function and of the min. HW temperature
«T2 min».
18. Days absent
DaysAbs
1
•
1-99
Individual specification of days absent
(if «Manual» was selected under point 17).
The HW temperature can be reduced as
low as «T2 min»
19. Remaining days absent
Days
0
•
0-99
Display of the remaining days absent.
20. Boost function
Boost
OFF
•
«OFF»
«ON»
Is activated to cover a short-term increased
need for HW. The BOOST function uses
maximum power «HP+EL» until «T max» is
reached, or for a maximum of 1 hour.
21. Fan
FanPause
OFF
•
«OFF»
«15»
«30»
When activated, the fan will be paused for
15 or 30 seconds per hour of operation.
8
4 215 949 / 00
OPerATIOn