Installation manual
12
Bela08+16I3
Hoval BelariaSRM
4P330420-1A – 2012.11
4 211 846 / 00 – 11/12
4 Configuration
Thermostats
Digital I/O PCB
Alarm output logic
Demand PCB
Energy metering
4.2.4 Quick wizard: Capacities (energy metering)
#
Code
Description
[A.2.2.4]
[C-05]
External room thermostat for the
main
zone:
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only send
a thermo ON/OFF condition. No
separation between heating or
cooling demand.
2 (C/H request): When the used
external room thermostat can send
a separate heating/cooling thermo
ON/OFF condition.
[A.2.2.5]
[C-06]
External room thermostat for the
additional
zone:
0: N/A
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only send
a thermo ON/OFF condition. No
separation between heating or
cooling demand.
2 (C/H request): When the used
external room thermostat can send
a separate heating/cooling thermo
ON/OFF condition.
[A.2.2.B]
[C-08]
External sensor:
0 (No): NOT installed.
1 (Outdoor sensor): Connected to
PCB measuring the outdoor
temperature.
2 (Room sensor): NOT applicable.
#
Code
Description
[A.2.2.6.1]
[C-02]
External backup heat source:
0 (No): None
1 (Bivalent): Gas, oil boiler
2: N/A
3: N/A
[A.2.2.6.3]
[C-09]
Alarm output on optional
SammelalarmBS PCB:
0 (Normally open): The alarm
output will be powered when an
alarm occurs.
1 (Normally closed): The alarm
output will NOT be powered when
an alarm occurs. This installer
setting allows distinction between
detection of an alarm and
detection of a power failure to the
unit.
See also table below (Alarm output
logic).
[A.2.2.6.4]
[F-04]
Bottom plate heater
0 (No): NOT installed
1 (Yes): Installed
[C-09]
Alarm
No alarm
No power
supply to unit
0 (default)
Closed output
Open output
Open output
1
Open output
Closed output
#
Code
Description
[A.2.2.7]
[D-04]
Demand PCB
Only applicable for Bela08 and
Belar08. Indicates if the
optional demand PCB is installed.
0 (No): NOT installed
1 (Yes): Installed
#
Code
Description
[A.2.2.8]
[D-08]
Optional external kWh meter 1:
0 (No): NOT installed
1: Installed (0.1 pulse/kWh)
2: Installed (1 pulse/kWh)
3: Installed (10 pulse/kWh)
4: Installed (100 pulse/kWh)
5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D-09]
Optional external kWh meter 2:
0 (No): NOT installed
1: Installed (0.1 pulse/kWh)
2: Installed (1 pulse/kWh)
3: Installed (10 pulse/kWh)
4: Installed (100 pulse/kWh)
5: Installed (1000 pulse/kWh)
#
Code
Description
[A.2.3.1]
[6-02]
Booster heater capacity [kW]
[A.2.3.6]
[6-07]
Bottom plate heater capacity [W]