background image

16

A draft reading of .05 to .06 w.c. is suggested for proper burning of this unit when using bituminous 

coal as fuel. When using anthracite coal, this draft reading is a minimum reading.

CAUTION

A chimney fire may cause ignition of wall studs or rafters which you thought were a safe distance from 

the chimney.  If you have a chimney fire, have your chimney inspected by a qualified person before 

using again.

EFFICIENCIES

 

Efficiencies can be based on either the lower heating value 

(LHV) or the higher heating value (HHV) of the fuel. The lower 

heating value is when water leaves the combustion process 

as a vapor. The higher heating value is when water leaves 

the combustion process completely condensed. 

OVER FIRING

Attempts to achieve heat output rates that exceed heater design 

specifications can result in permanent damage to the heater.

ASH REMOVAL AND DISPOSAL 

Whenever ashes get 3 to 4 inches deep in your firebox or ash 

pan, and when the fire has burned down and cooled, remove 

excess ashes. Leave an ash bed approximately 1 inch deep 

on the firebox bottom to help maintain a hot charcoal bed.
Ashes  should  be  placed  in  a  metal  container  with  a  tight-

fitting lid. The closed container of ashes should be placed 

on a noncombustible floor or on the ground, away from all 

combustible  materials,  pending  final  disposal.  The  ashes 

should be retained in the closed container until all cinders 

have thoroughly cooled.

SMOKE AND CO MONITORS

CO is a poisonous gas when exposed to elevated concentrations 

for extended periods of time. While the modern combustion 

systems in heaters drastically reduce the amount of CO emitted 

out the chimney, exposure to the gases in closed or confined 

areas can be dangerous. Make sure your stove gaskets and 

chimney joints are in good working order and sealing properly 

to ensure unintended exposure. It is recommended that you 

use both smoke and CO monitors in areas having the potential 

to generate CO. 

GASKETS

It is recommended that you change the door gasket (which 

makes  your  stove  door  air  tight)  once  a  year,  in  order  to 

insure good control over the combustion, maximum efficiency 

and security. To change the door gasket, simply remove the 

damaged one. Carefully clean the available gasket groove, 

apply a high temperature silicone sold for this purpose, and 

install  the new gasket. You may light  up your stove again 

approximately 24 hours after having completed this operation. 

This unit’s ash door uses a 5/8" diameter rope gasket. This 

unit's feed door uses a 1/2" diameter rope gasket.

SERVICE HINTS

Do not expect a furnace to draw.  It is the chimney that 

creates the draft.  Smoke spillage into the house or 

excessive build-up of water or creosote in the chimney 

are warnings that the chimney is not functioning properly.

 

Correct the problem before using furnace.  Possible causes are:

1. 

The connector pipe may be pushed into the chimney too 

far, stopping the draft.

2. 

Do not connect two furnaces or a stove and furnace into 

the same chimney flue.

3. 

The  chimney  used  for  a  furnace  must  not  be  used  to 

ventilate the cellar or basement.  If there is a cleanout 

opening at the base of the chimney, it must be closed tightly.

4.  If the chimney is operating too cool, water will condense 

in the chimney and run back into the furnace.  Creosote 

formation will be rapid and may block the chimney.  Operate 

the furnace at a high enough fire to keep the chimney 

warm, preventing this condensation.

5. 

If the  fire  burns  well,  but  sometimes  smokes  or  burns 

slowly, it may be caused by the chimney top being lower 

than another part of the house or a nearby tree.  The 

wind blowing over a house or a tree, falls on top of the 

chimney like water over a dam, beating down the smoke.  

The top of the chimney should be at least 3 feet above 

the roof and be at least 2 feet higher than any point of 

the roof within 10 feet.

CHIMNEY MAINTENANCE

Creosote and Soot - Formation and Need for Removal
When coal is burned, the products of combustion combine with 

moisture to form a soot residue which accumulates on the flue 

lining.  When ignited, this soot makes an extremely hot fire.
The  chimney  should  be  inspected  at  least  twice  monthly 

during the heating season to determine if a creosote or soot 

build up has occurred.
If creosote or soot has accumulated, it should be removed to 

reduce the risk of a chimney fire.
Chimney  fires  burn  very  hot.    If  the  chimney  catches  fire, 

immediately call the fire department, then reduce the fire by 

closing the inlet air control.  Pour a large quantity of coarse 

salt, baking soda or cool ashes on top of the fire in the firebox.

ATTENTION:

This heater needs periodic inspection and repair for proper operation. It is against federal regulations 

to operate this heater in a manner inconsistent with operating instructions in this manual.

Summary of Contents for 1357M

Page 1: ... FORCED AIR GAS OR OIL FIRED FURNACE U S ONLY FOR INSTALLATION AS A CENTRAL FURNACE ALL MODELS CERTIFIED UNDER UL 391 85591V 0602G CAUTION READALLINSTRUCTIONSCARE FULLY BEFORE STARTING THE INSTALLATIONOROPERATING THE FURNACE IMPROPER INSTALLATION MAY VOID YOUR WARRANTY DO NOT USE THIS FURNACE IN A MOBILE HOME OR TRAILER U S Environmental Protection Agency Certified to comply with 2015 particulate ...

Page 2: ...er or 5 16 Socket W Ratchet Safety Glasses MATERIAL 6 Pipe 6 Elbow Collar and Thimble as required 24 gauge min 1 2 Sheet Metal Screws 6 Inside diameter Listed Residential Type or Building Heating Appliance Chimney or existing masonry chimney Electrical Wiring 6 Draft Regulator 1 2 Conduit Conduit Connectors Furnace Cement Manufacturer Recommends Rutland Black Code 78 or Equivalent Plenum and Duct ...

Page 3: ...AFETY NOTICE If this heater is not properly installed a house fire may result For your safety follow the installation directions Contact local building or fire of ficials about restrictions and installation inspection requirements in your area If not already installed we recommend that smoke detectors be installed CAUTION CLEANOUT OF THE HEAT EXCHANGER FLUE PIPE CHIMNEY AND DRAFTINDUCER IFUSED ISE...

Page 4: ...A 211 The address of the NFPA is Batterymarch Park Quincy MA 02269 11 Keep the ashpit section free of excess ashes Do not al low ashes to stack higher than the sides of the ash pan 12 DISPOSAL OFASHES Place ashes in a metal container with a tight fitting lid Keep the closed container on a noncombustible floor or on the ground well away from all combustible materials Keep the ashes in the closed co...

Page 5: ...TRAL FURNACE INSTALLATION As a central furnace the unit functions independently of any other system The blower will come on when the plenum temperature reaches the setting on the blower control PARALLEL INSTALLATION U S ONLY The design is such that when the blower comes on the blower on the central system also comes on The blower will only come on when the temperature in the plenum has reached the...

Page 6: ...6 Figure 2 Model 1557M Figure 1 Model 1357M DIMENSIONS OF FURNACE ...

Page 7: ...ble surfaces If you have a solid brick or stone wall behind your furnace you can place the furnace as close as you wish to the wall If the wall is only faced with brick or stone treat it as a combustible wall 18 18 6 SOLID DAMPER 6 BAROMETRIC DRAFT REGULATOR NON COMBUSTIBLE FLOOR 12 9 48 18 CENTRAL FURNACE 6 CHIMNEY 21 Figure 4 Figure 5 1357M 1557M Unit to Sidewall 12 305mm 12 305mm Unit to Backwa...

Page 8: ...manufacturer s instructions Use only a Listed Residential Type or Building Heating Appliance Chimney If your chimney starts at the ceiling Fig 7 you will need enough 6 pipe to reach the ceiling The top of the chimney must be at least 3 feet above the roof and be at least 2 feet higher than any point of the roof within 10 feet Fig 7 IMPORTANCE OF PROPER DRAFT Draft is the force which moves air from...

Page 9: ... same room same pressure zone as the furnace 8 Install the barometric draft regulator strictly in accordance with the instructions that are provided with the barometric draft regulator 9 A solid damper must be used in the chimney connecting pipes be tween the flue collar and the chimney When used in conjunction with a barometric draft regulator the solid damper must be placed between the barometri...

Page 10: ...ow to connect the chimney connector of a heater to a masonry chimney through a combustible wall There are five allowable ways that a chimney connector can be connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems Figure 11 ...

Page 11: ...ATTACH CONNECTOR SECURELY AIR SPACE inner surface of the chimney flue and shall be firmly cemented in place See Part A 2 Use a solid insulated listed factory built chimney length having an inside diameter of 6 and having 1 or more of solid insulation There must be at least a 9 air space between the outer wall of the chimney length and any combustible materials The inner end of the chimney length s...

Page 12: ... thermal conductivity of 1 0 Btu in ft F 4 88 kg cal hr m C or less 2 All clearances and thicknesses are minimums larger clear ances and thickness are acceptable 3 A chimney thimble as shown for 3 and 4 above Parts C and D shall be for types 3 and 4 connections to facili tate removal of the chimney connector for cleaning The chimney thimble shall be of ASTM C315 fireclay with 5 8 minimum wall thic...

Page 13: ...uired to lock feed door during firing sequence 4 Install the thermodisc on rear of furnace cabinet with the two screws provided Mount the conduit assembly from the junction box to the thermostat bracket Crimp the two female terminals to each of the wire leads Plug the wires to the thermodisc NOTE It does not matter which of the two wires plugs to which terminal on the thermodisc 5 Remove blowers f...

Page 14: ... wiring wires M1 M2 of one blower motor Wire leads from the distribution blower are usually BOTH BLACK Makes no difference which leads from the motor s connects to the corresponding leads coming out of the conduit Figure 16 WIRING DIAGRAM ...

Page 15: ...specificmodel Sealthesmokepipeinthechimneywithfurnacecement The chimney connector shall be securely supported and joints fastened with sheet metal screws or rivets e Install 8 diameter heat pipe to plenum of the central hot air furnace Use 26 gauge pipe and connectors to be purchased separately If central air conditioning is installed in the plenum install heat pipe above the air conditioning unit...

Page 16: ...this purpose and install the new gasket You may light up your stove again approximately24hoursafterhavingcompletedthisoperation This unit s ash door uses a 5 8 diameter rope gasket This unit s feed door uses a 1 2 diameter rope gasket SERVICE HINTS Do not expect a furnace to draw It is the chimney that creates the draft Smoke spillage into the house or excessive build up of water or creosote in th...

Page 17: ...el B Check length of flue pipe to chimney Your unit should be within six 6 feet of your chimney C Make sure chimney cap is not too close to the top of the chimney D Check chimney draft make sure chimney flue pipe is clean and chimney is of adequate height E Slide baffle should be pulled out prior to load door opening 4 Problem Distribution blower vibrating Solution A Tighten blower wheel to motor ...

Page 18: ...18 Repair Parts 22 6 8 7 9 20 18 19 17 16 14 10 15 11 12 13 21 1 5 2 3 4 1 28 27 26 29 30 31 24 25 32 33 23 35 34 38 37 36 40 38 36 37 39 34 42 41 46 48 47 44 43 45 49 1357M 1557M 69399 ...

Page 19: ...wer 1357M 1 1557M 2 27 89319 Gasket Blower 1357M 1 1557M 2 28 83340 1 4 20 Clipnut 1357M 4 1557M 8 N S 83339 Bolt 1 4 20 x 3 4 1357M 4 1557M 8 29 22140 Relay Box Bracket 1 30 80131 Junction Box 4 x 4 1 31 80231 Junction Box Cover 1 32 80314 Thermodisc 60T12 1 33 68234 Blower Thermostat Bracket 1 34 89066 Firebrick 4 5 x 9 x 1 25 1357M 10 1557M 12 35 40264 Liner Front Rear 1357M 2 36 40256 Grate Fr...

Page 20: ...uses a standard 16 x 20 x 1 filter NOT INCLUDED to reduce the amount of dust particles from being transfered thru you duct work system DR 6 BAROMETRIC DAMPER REGU LATOR In the unlikely event that your furnace overfires a con dition evidenced by elbows stove pipes and connectors glowing red in appearance or otherwise discoloring then your installation is subject to excessive draft cre ated by eithe...

Page 21: ...himney s or installations are going to be the same Just remember to allow enough air to enter the firebox and keep the stove pipe damper open so that volatiles are properly burned Before refueling take the time to break up the cone a little with a poker especially if it has caked over or formed a crust But be careful not to mix the coal as this increases the chances of forming clinkers When shakin...

Page 22: ...efueling If possible avoid shaking as a heavier layer of ash will help reduce the intensity of the fire during this time After loading let the fire establish itself for about 30 minutes Then close your damper and automatic control to the point where the house does not become too cold It is important that you begin banking early enough before retiring or leav ing that you can make necessary adjustm...

Page 23: ...23 CENTRAL INSTALLATION CENTRAL INSTALLATION ADD ON INSTALLATION ...

Page 24: ...AIR RETURN TOEXISTING DUCTWORK WARMAIR EXISTING FURNACE SOLIDFUEL FURNACE FILTERBOX PLENUM COLLECTOR BOX COLDAIR RETURN TOEXISTING DUCTWORK WARMAIR EXISTING FURNACE SOLIDFUEL FURNACE FILTERBOX COLDAIR RETURN PLENUMTOP OPTIONAL Appendix INSTALLATION A INSTALLATION B INSTALLATION C ...

Page 25: ...25 INSTALLATION D INSTALLATION E ...

Page 26: ...26 INSTALLATION F INSTALLATION G ...

Page 27: ...27 INSTALLATION H TOP VIEW FRONT VIEW ...

Page 28: ...ompany ________________________________________ Telephone No ______________________________________ Stove Inspected Chimney Swept Items Replaced ____________________________________ Service 05 Date ________________________ Engineer Name _____________________________________ Company __________________________________________ Telephone No ______________________________________ Stove Inspected Chimne...

Page 29: ... 4 Damage or defect caused by improper installation accidents misuse abuse including overfiring or alteration 5 Transportation or shipping costs LIMITATIONS AND EXCLUSIONS 1 United States Stove Company shall not be liable for incidental consequential special or contingent damages anyone might suffer as a result of their breach of this written warranty or any implied warranty 2 Should the heater be ...

Page 30: ...30 NOTES ...

Page 31: ...31 NOTES ...

Page 32: ...CHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMA TION AS SHOWN IN THIS LIST 1 THE PART NUMBER__________________________________ 2 THE PART DESCRIPTION______________________________ 3 THE MODEL NUMBER________________________________ 4 THE SERIAL NUMBER________________________________ United States Stove Company 227 Industrial Park Road P O Box 151 South Pittsburg TN 3...

Reviews: