Heat Pump Water Heater Installation Guide

Installation Procedure

1. Mounting System
a) Outdoor Mounting. 

Use accessory HPOMK. Lay the unit on its side using 

the cardboard packing as protection. Attach the plastic mounting feet to the 

underside of the unit using the cap screws provided. 

b) Ceiling Installation. 

Use only accessory HPCMK. Mount the ceiling tray 

in the roof space in a suitable location. The unit should then be placed on the 

drip tray and secured in place using the seismic restraints, which should be 

attached to the side of the unit and to the support beams. 

Please note: Adequate access and room for service must be allowed for the 

tradesperson’s safety and to prevent potential property damage. Any damage 

caused to private property due to incorrect installation, including damage 

caused whilst rectifying faults, is not covered under warranty. 

1. 

Ceiling  access  must  be  large  enough  to  allow  the  heat  pump  to  fit 

through it easily. 

2.  A walkway must be installed from the access point to the heat pump. 

3.  The heat pump must be located on a platform at least 2m x 2m and a 

minimum height requirement at heat pump of 1500mm to allow working 

room around the heat pump. 

4.  A light of at least 12W LED must be installed above the heat pump. 

c) Wall Mounting. 

Use accessory HPWMK. Mount wall brackets using level 

onto  concrete  block  wall.  Place  anti-vibration  mounts  supplied  onto  wall 

brackets. Screw up into unit using 4x capscrews (supplied).

d) Closed Garage Installations. 

Cold air leaving the unit must be ducted to 

the outside without loss of air flow. A fresh air supply must also be installed to 

ensure that the correct air flow through the heat pump is maintained.

1. 

Windows are insufficient for this purpose.

2.  Ensure no objects can be placed within 500mm of the heat pump as 

this will reduce its efficiency. 

3.  Allow for drainage of water naturally produced by the cooling coil 

(evaporator) from within the heat pump. 

Adequate access and space for service must 

be allowed for all types of installation

!

Summary of Contents for Econergy EC L Series

Page 1: ...Heat Pump Water Heater Installation Guide FOR QUALIFIED PERSONNEL ONLY...

Page 2: ......

Page 3: ...8 Installation 10 Installation Procedure 13 Piping Diagram 14 Commissioning 19 Troubleshooting 20 Important Information 22 Wiring Diagram 23 Hot Water Cylinder Specifications 24 Heat Pump Specificati...

Page 4: ...ce where the unit is going to be located For installation to existing homes the unit should be installed with a maximum insulated pipe run of 9 metres For new homes the layout should be designed so th...

Page 5: ...s close as possible to the HWC to ensure best efficiency This is because each leg of supply return piped water loses its heat during the off cycle despite being insulated The cylinder should be locate...

Page 6: ...if this was specified or required by the customer then the piping design as per wetback must be designed to avoid thermosyphoning of high temperature water through the unit while not running Hot Wate...

Page 7: ...rranty Use of Econergy heat pump ready cylinders avoids any potential warranty issues resulting from modification to fit sensor pockets B Retrofit Retrofit can be made to any electric hot water cylind...

Page 8: ...cation Picture Outdoor Mounting Kit For mounting outdoors under houses on flat surfaces HPOMK Ceiling Mounting Kit For mounting in ventilated accessible ceiling cavities HPCMK Roof Mounting Kit For mo...

Page 9: ...ot water cylinders HPGRK Coopers Solar Ready Retrofit Kit For retrofit to Coopers Solar Ready Hot Water Cylinders HPCRK Dux Rinnai Retrofit Kit For retrofit to Dux Proflow and Rinnai Hotflow Hot Water...

Page 10: ...PEX Fusiotherm Copper AS NZS compliant 2 Pipe Line Fittings Dux Secura REHAU Fusiotherm Kembla PEX or AS NZS Standard DR brass fittings 3 Flexible Hoses NOT ALLOWED 4 Ball Valves Use only full flow 1...

Page 11: ...inth height 100 min distance from wall min distance from wall min distance from wall installed unit height 610 min distance from wall hot water cupboard 650 600 400 400 min distance from wall 200 200...

Page 12: ...Roof Cavity Support beams Seismic restraint wires Drain Ensure ceiling is ventilated At least 600mm clearance Support beams Seismic restraint wires Drain Ensure ceiling is ventilated At least 600mm c...

Page 13: ...rranty 1 Ceiling access must be large enough to allow the heat pump to fit through it easily 2 A walkway must be installed from the access point to the heat pump 3 The heat pump must be located on a p...

Page 14: ...h kit Screw 2x 50x50 AL angles supplied into side of unit Place angles across mounting rails of roof mounting kit Using M10 SS bolts supplied bolt down through anti vibration mounts into spring nuts i...

Page 15: ...n good condition 2 Fitting of Tank Sensor kit HPTSK may void HWC s manufacturer warranty 3 Ensure minimum pressure of 50kPa met on low pressure installations may require fitting of relief valve to ope...

Page 16: ...line to heat pump to solar connection 2 Ensure minimum pressure of 50kPa met on low pressure installations may require fitting of relief valve to open vent HWC Piping Diagram Coopers Heat Pump Ready...

Page 17: ...t cover Mixing Valve 20mm Outlet Hot Water Backup Module Cold Water Expansion Valve 15mm 20mm 20mm Pressure Reducing Valve 20mm 20mm Ball Valve Ball Valve Stop Valve Check Valve Mains Supply Regulated...

Page 18: ...trunking to the hot water cylinder location 5 Tank Sensor Mounting a Econergy Hot Water Cylinder This comes with dual sensors upper and lower Insert the lower tank sensor into the pocket about 1 3 of...

Page 19: ...isconnection must be incorporated in the fixed wiring A Certificate of Compliance must be issued by the installer 7 Condensate drain Condensate drains must be run in the following cases a Where the un...

Page 20: ...Fill system with water and leak test all connections at system pressure Check all electrical connections and ensure that water heater is securely grounded to the building s earthing point Ensure both...

Page 21: ...50 C Tidy up installation If there is time then check that the whole tank has heated successfully otherwise check back later and use the Econergy Config software to download the events log to ensure t...

Page 22: ...inputs on PCB or damaged CAT 5 cable Remove HWB panel and cover on main electrical box Check that all sensors are plugged into their correct locations and the CAT 5 cable is securely plugged in and un...

Page 23: ...essible to the general public The appliance is not intended for use by young children or infirm persons without supervision Young children shall be supervised to ensure they do not play with the appli...

Page 24: ...k Temperature Hot Water Cylinder Ttl Lower Tank Temperature Backup Element RJ45 Data Cable Ttu J5 Ttl J4 240VACUncontrolled 240VACControlled To HWC To HP Unit Phase Neutral Earth Neutral Phase Earth H...

Page 25: ...Water Heater Installation Guide Hot from heat pump 45 45 470 Outlet TPR valve Temperature sensor top Top element Temperature sensor bottom Solar return or probe port Cold to heat pump E 470 User adj t...

Page 26: ...470mm from Cylinder Jacket Top Temperature Sensor 43 L 60 L 60 L Storage capacity at 470mm from Cylinder Jacket Bottom Temperature Sensor 44 L 59 L 59 L Weight Empty 37 5 kg 51 5 kg 61 kg Inlet Outle...

Page 27: ...R 134a Refrigerant quantity 590 gm Ambient Air Temperature 5 to 40 C Performance Specifications HP4000LT Heat output 3600 W Rated input 1000 W Recovery rate 67 L hr Efficiency COP 3 8 W W Water Conne...

Page 28: ...0800 33 66 33 www waterheating co nz Phone 09 838 9444 Email info waterheating co nz 3 Corban Ave Henderson Auckland 0612 PO Box 21 586 Henderson Auckland 0650...

Reviews: