F. Electrical Connection
WARNING
1. Electrical connections must be made in accordance with the instructions on
the "WARNING" tag, provided with the pig tail leads in the condensing unit
junction box.
2. Electrical connections must meet national, state, and local electrical code
requirements. Failure to meet these code requirements could cause severe
injury to individuals or extensive damage to equipment.
3. Be sure to install a proper ground to the condensing unit.
4. Power supply and ground wire to the icemaker are supplied from the
condensing unit via the wire harness. Connect the icemaker and condensing
unit using the wire harness supplied, or fabricate a wire harness using
appropriate outdoor-rated 18 AWG wire. Use the wiring label or Fig. 8 as a
reference when making connections.
• Electrical connections must be installed in accordance with applicable national, state, and
local regulations.
• Usually an electrical permit and services of a licensed electrician are required
• The condensing unit requires an independent power supply. See the nameplate for proper
voltage and breaker/fuse size.
• Power supply and ground wire to the icemaker are supplied from the condensing unit via
the wire harness.
• The maximum allowable voltage variation is ±10 percent of the nameplate rating.
• On single phase machines, the white lead must be connected to the neutral conductor of
the power source. Miswiring results in severe damage to the icemaker. See Fig. 6.
• On three phase machines, the transformer's voltage tap switch must be positioned to
match incoming voltage at startup. See Fig. 7.
1. Icemaker
Power supply and ground wire to the icemaker are supplied from the condensing unit
via the wire harness. Connect the icemaker and condensing unit using the wire harness
supplied, or fabricate a wire harness using appropriate outdoor-rated 18 AWG wire.
WARNING
To reduce the risk of electric shock, do not connect the power supply until after
all wire harness connections have been made.
1) Route the wire harness from the icemaker to the condensing unit.
2) Secure the wire harness to the condensing unit with the strain relief bushing provided
(condensing unit accessory).