13
[d] Electrical Connection
WARNING
1. This condensing unit must have a separate power supply. See the
nameplate.
2. This condensing unit requires a ground that meets the national and local
electrical code requirements. To prevent possible electrical shock to
individuals or extensive damage to equipment, install a proper ground wire to
this condensing unit.
• The opening for the power supply connection is 7/8" DIA to fit a 1/2" trade size conduit.
• Usually an electrical permit and services of a licensed electrician are required.
• Installation of an external power disconnect may be required by local code.
1) Remove the louver panel.
2) Remove the control box cover.
3) Connect the three loose leads in the control box to the power supply.
Note: The white lead must be attached to the neutral line.
4) Replace the control box cover and the louver panel in their correct positions.
Note: The icemaker and condensing unit have independent power supply circuits.
Fig. 6
5) Remove the plastic caps protecting the couplings. Apply two drops of POE oil to the male
threads of the couplings. Attach the two refrigerant lines to the male couplings on the
icemaker and the remote condensing unit. The couplings must be tightened 1/4 turn
beyond fully seated. Each refrigerant line must be connected as follows:
Icemaker suction refrigerant line - 5/8" OD tubing
Icemaker liquid refrigerant line - 1/4" OD tubing
Note: Make the connections at the remote condensing unit first and then at the icemaker.