Everest Glycol System Chiller
lancerbeverage.com
Page 7 of 13
Hoshizaki Lancer reserve the right to change specifications without notice
No 007 – 5 November 2010
6. Thermostat, Settings & Programming
Carel
Parameter set 1
Type
Def
Description
/tl F
1
1 = glycol probe displayed,
/c1 C
0.0
Calibration of glycol probe if required, generally should be 0.0
St F
-2.0
Set point, refrigeration will turn off at this temperature
rd F
1.0
Differential, glycol temp will increase from the cut out point by this
value before the refrigeration turns on.
r1 F
-5.0
Minimum allowed set point
r2 F
5.0
Maximum allowed set point
r3 C
1
1 = cooling only no defrost
r4 C
6.5
Value to increase the set point by if the digital input is closed (optional
switch)
r5 C
1
1 = temperature logging enabled
while in LO or HI reading press set key to reset
rt C
Period of temperature logging (hrs)
rH F
Highest temp recorded over previous time span (rt)
rL F
Lowest temp recorded over previous time span
c2 C
3
Minimum time after turning off before the control will give an output to
the refrigeration solenoid
AL C
4.0
Low temperature alarm, 4° below the set point (relative)
Controls programmed during manufacture by key.
If reset is required in field:
Turn unit off, hold PRG key and restore power.
On power up the control will default to Carel base settings.