6. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND LINE
VALVE
CAUTION
Always use a copper tube of the same diameter and length when replacing
the hot gas lines; otherwise the performance may be reduced.
IMPORTANT
Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier until after all other repair or replacement
has been made.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the Solenoid.
5) Disconnect the Hot Gas Valve or Line Valve using brazing equipment.
6) Install the new valve.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 250°F.
7) Install the new Drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. For air-cooled and water-
cooled models, see the Nameplate for the required refrigerant charge. For remote
air-cooled models, see the Charge Label in the machine compartment.
Summary of Contents for KML "F" SERIES
Page 6: ...6 I SPECIFICATIONS 1 KML 250MAH...
Page 7: ...7 2 KML 250MWH...
Page 8: ...8 3 KML 350MAF...
Page 9: ...9 4 KML 350MWF...
Page 10: ...10 5 KML 350MAH...
Page 11: ...11 6 KML 350MWH Beginning serial L00001J ending Serial M20060C...
Page 12: ...12 7 KML 350MWH Beginning serial M30061E...
Page 13: ...13 8 KML 450MAF...
Page 14: ...14 9 KML 450MWF...
Page 15: ...15 10 KML 450MAH...
Page 16: ...16 11 KML 450MWH Beginning Serial L00001D ending Serial M10530B...
Page 17: ...17 12 KML 450MWH Beginning Serial M20531D...
Page 18: ...18 13 KML 600MAF...
Page 19: ...19 14 KML 600MWF...
Page 20: ...20 15 KML 600MRF...
Page 21: ...21 16 KML 600MAH...
Page 22: ...22 17 KML 600MWH Beginning Serial L00001D ending Serial M10115C...
Page 23: ...23 18 KML 600MWH Beginning Serial M10121E...
Page 24: ...24 19 KML 600MRH...
Page 25: ...25 20 CONDENSER UNIT URC 7F Unit mm inches...
Page 26: ...26 SPECIFICATIONS URC 7F...
Page 48: ...48 b KML 250MWH KML 350MWF KML 350MWH KML 450MWF KML 450MWH KML 600MWF KML 600MWH...
Page 49: ...49 c KML 600MRF KML 600MRH...
Page 65: ...65 4 PERFORMANCE DATA a KML 250MAH...
Page 66: ...66 b KML 250MWH...
Page 67: ...67 c KML 350MAF...
Page 68: ...68 d KML 350MWF...
Page 69: ...69 e KML 350MAH...
Page 70: ...70 f KML 350MWH Serial L00001J through M20060C...
Page 71: ...71 g KML 350MWH Beginning Serial M30061E...
Page 72: ...72 h KML 450MAF...
Page 73: ...73 i KML 450MWF...
Page 74: ...74 j KML 450MAH...
Page 75: ...75 k KML 450MWH Serial L00001D through M10530B...
Page 76: ...76 l KML 450MWH Beginning Serial M20531D...
Page 77: ...77 m KML 600MAF...
Page 78: ...78 n KML 600MWF...
Page 79: ...79 o KML 600MRF...
Page 80: ...80 p KML 600MAH...
Page 81: ...81 q KML 600MWH Serial L00001D through Serial M10115C...
Page 82: ...82 r KML 600MWH Beginning Serial M10121E...
Page 83: ...83 s KML 600MRH...