14
f) Freeze Timer (S1 dip switch 9 & 10)
The freeze timer setting determines the maximum allowed freeze time to prevent possible
freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After
2 consecutive timer terminations, machine will shut down, possibly indicating a problem.
The freeze timer is factory adjusted, and no adjustment is required.
g) Pump-Out Pump Motor Delay (S2 dip switch 1)
The pump-out pump motor delay determines whether or not the pump motor de-energizes
for 2 seconds before restarting at the beginning of a drain cycle.
The pump-out pump motor delay is factory adjusted and no adjustment is required.
S2 Dip Switch Setting
No. 1
Delay
(seconds)
OFF 0
ON 2
Control Board P00013-02
h) Refill Counter (S2 dip switch 2, 3, & 4) [Program Ver. 2.5 or earlier]
Do not adjust. These must be left in the factory default position or the unit will not operate
properly. The KMD-410MAH and KMD-410MWH refill 1 time.
i) Factory Use (S2 dip switch 5) [Program Ver. 2.5 or earlier]
Must remain off.
j) Anti-Slush Control (S2 dip switch 6) [Program Ver. 2.5 or earlier]
The anti-slush control (Ver. 1.0) helps prevent slushing during the freeze cycle on small
icemakers.
It is deactivated on the KMD-410 series.
When activated, the thermistor located on the suction line checks for a 34°F (1°C)
temperature as the evaporator cools. When 34°F (1°C) is reached, a 5.9 k signal causes
the control board to de-energize the pump motor for 10 seconds.
Do not adjust. This must be left in the factory default position or the unit will not operate
properly.