24
e) Freeze Timer
CAUTION
Adjust to proper specification, or the unit may not operate correctly.
The freeze timer is factory adjusted and no adjustment is required. This setting
determines the maximum allowed freeze time to prevent possible freeze-up issues.
No. 9
No. 10
OFF
OFF
60
OFF
ON
50
ON
OFF
70
ON
ON
75
Dip Switch Setting
Time
(minutes)
c) Drain Timer
The drain timer is factory-adjusted and no adjustment is required.
T1: Time to drain the water tank
T2: Time to restrain defrost completion
d) Drain Counter
CAUTION
Do not adjust the drain counter, or the evaporator may freeze up.
The drain counter is factory-adjusted to drain the water tank every 10 cycles, and no
adjustment is required. However, where water quality is bad and the icemaker needs a
pump drain more often, the drain counter can be adjusted as shown in the table below.
No. 3
No. 4
T1
T2
OFF
OFF
10
150
ON
OFF
10
180
OFF
ON
10
120
ON
ON
20
180
Dip Switch Setting
Time (seconds)
No. 5
No. 6
OFF
OFF
every cycle
ON
OFF
every 2 cycles
OFF
ON
every 5 cycles
ON
ON
every 10 cycles
Dip Switch Setting
Frequency