20
2nd Cycle and after with pump drain
1. Float switch opens and signals to complete
freeze cycle.
Drain timer starts counting.
2. Drain timer stops counting.
Pump drain is completed.
3. Thermistor reads 9°C.
Defrost timer starts
counting.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when float
switch circuit opens.
4. Defrost timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if defrost timer does not stop counting.
IMPORTANT
Water valve
opening is limited
to 6 minutes.
IMPORTANT
Freeze cycle time is limited by the freeze timer
factory setting even if the float switch does not
open.