54
9) Float Switch
The Float Switch or connector may have a bad contact if the Float Switch trips at the upper
float level but not at the lower float level with the Flush Water Valve closed. “E2” will appear
in the Display Window.
10) High Pressure Switch
Operates at a high condensing pressure when the icemaker has a clogged Air Filter or a
dirty Condenser. “E4” will appear in the Display Window when the Pressure Switch trips five
times within an hour.
11) Voltage
If the supply voltage is too low, the Compressor may fail to start properly, or the Gear Motor
may lock to cause freeze-up inside the Evaporator. To prevent these troubles, the icemaker
will shut down and wait until the proper voltage is restored. “EF” will appear in the Display
Window.
Summary of Contents for FM-300AFE-HC
Page 7: ...3 2 DIMENSIONS CONNECTIONS a FM 481AGE HC FM 481AGE HCN ...
Page 8: ...4 b FM 300AFE HC FM 300AFE HCN ...
Page 9: ...5 3 SPECIFICATIONS a FM 481AGE HC ...
Page 10: ...6 b FM 481AGE HCN ...
Page 11: ...7 c FM 300AFE HC ...
Page 12: ...8 d FM 300AFE HCN ...
Page 14: ...10 Drier Ice Chute Pressure Switch ...
Page 23: ...19 b FM 300AFE HC FM 300AFE HCN Pressure Switch Cut out 22 6 1 5 0 bar Cut in 15 7 1 5 bar ...
Page 24: ...20 2 WIRING DIAGRAM a WIRING DIAGRAM FM 481AGE HC FM 481AGE HCN ...
Page 25: ...21 FM 300AFE HC FM 300AFE HCN ...
Page 26: ...22 b CONTROL BOX LAYOUT FM 481AGE HC FM 481AGE HCN ...
Page 27: ...23 FM 300AFE HC FM 300AFE HCN ...
Page 35: ...31 FM 300AFE HC FM 300AFE HCN ...
Page 36: ...32 ...
Page 37: ...33 c SEQUENCE FM 481AGE HC FM 481AGE HCN 1 Startup Water Supply ...
Page 39: ...35 FM 481AGE HC FM 481AGE HCN 3 Startup Ice production starts ...
Page 40: ...36 FM 481AGE HC FM 481AGE HCN 4 Normal Operation Bin Control ...
Page 41: ...37 FM 481AGE HC FM 481AGE HCN 5 Shutdown Compressor stops 5 min ...
Page 42: ...38 FM 481AGE HC FM 481AGE HCN 6 Shutdown Drain ...
Page 43: ...39 FM 300AFE HC FM 300AFE HCN 1 Startup Water Supply ...
Page 45: ...41 FM 300AFE HC FM 300AFE HCN 3 Startup Ice production starts ...
Page 46: ...42 FM 300AFE HC FM 300AFE HCN 4 Normal Operation Bin Control ...
Page 47: ...43 FM 300AFE HC FM 300AFE HCN 5 Shutdown Compressor stops 5 min ...
Page 48: ...44 FM 300AFE HC FM 300AFE HCN 6 Shutdown Drain ...