         Specifications / Installation

 

__________________________________________________________________________________________________________________________________________________________________ 

4/28/2009 

                                                                       Page 6 of 6                                                                                                                       ECN # 950 

 
 

Filter  

 

Filter Constant sets the level of digital filtering according to the following chart. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Digital Filtering.  The illustration above demonstrates the effect of digital filtering 

(set with Filter Constant) on module response to a temperature 
change. 

 
 

I/O Register Map 

 

 

Registers 

 

Description 

%I1 to %I24 

Digital Inputs 

%I32 

Output Fault 

%I25 to %I31 

Reserved 

%Q1 to %Q16 

Digital outputs 

%Q17 

Clear HSC1 accumulator to 0 

%Q18 

Totalizer: Clear HSC2 

Quadrature 1-2: Accumulator 1 

Reset to max – 1 

%Q19 

Clear HSC3 Accumulator to 0 

%Q20 

Totalizer: Clear HSC4 

Quadrature 3-4: Accumulator 3 

Reset to max – 1 

%Q21 to %Q32 

Reserved 

%AI1 to %AI4 

Analog inputs 

%AI5, %AI6 

HSC1 Accumulator 

%AI7, %AI8 

HSC2 Accumulator 

%AI9, %AI10 

HSC3 Accumulator 

%AI11, %AI12 

HSC4 Accumulator 

 

 

%AQ1, %AQ2 

PWM1 Duty Cycle 

%AQ3, %AQ4 

PWM2 Duty Cycle 

%AQ5, %AQ6 

PWM Prescale 

%AQ7, %AQ8 

PWM Period 

%AQ9 to %AQ14 

Analog outputs 

Note:  Not all XL6 units contain the I/O listed in this table. 

 
 

Registers 

PWM 

HSC 

Stepper 

%AQ1 

Start 

Frequency 

%AQ2 

PWM1 Duty 

Cycle 

(32 bit) 

HSC1 

Preset 

Value 

Run 

Frequency 

%AQ3 

%AQ4 

PWM2 Duty 

Cycle 

(32 bit) 

HSC2 

Preset 

Value 

Accel Count 

(32 bit) 

%AQ5 
%AQ6 

PWM Prescale 

(32 bit) 

 

Run Count 

(32 bit) 

%AQ7 
%AQ8 

PWM Period 

(32 bit) 

 

Decel Count 

(32 bit) 

 

 

 

 

%Q1 

 

 

Run 

%I30 

Ready/Done 

%I31 

 

 

Error 

 

Technical Support 

 

For assistance and manual updates, contact Technical Support at the following 
locations: 

 

North America:   
Tel:  317 916-4274 
Fax: 317 639-4279 
Web:    

http://www.heapg.com

  

Email:  

[email protected]

 

Europe:  
Tel:  +353-21-4321266 
Fax: +353-21-4321826 
Web:    

http://www.horner-apg.com

 

Email:  

[email protected]

 

 
 
 

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 All applicable codes and standards need to be followed in the installation of this product.   

  Adhere  to  the  following  safety  precautions  whenever  any  type  of  connection  is  made  to  the 

module:  

 

 

  Connect  the  safety  (earth)  ground  on  the  power  connector  first  before  making  any  other 

connections. 

 When connecting to electric circuits or pulse-initiating equipment, open their related breakers. 

 Do not make connections to live power lines. 

 Make connections to the module first; then connect to the circuit to be monitored. 

 Route power wires in a safe manner in accordance with good practice and local codes. 

  Wear  proper  personal  protective  equipment  including  safety  glasses  and  insulated  gloves 

when making connections to power circuits. 

 Ensure hands, shoes, and floors are dry before making any connection to a power line. 

 Make sure the unit is turned OFF before making connection to terminals. 

 Make sure all circuits are de-energized before making connections. 

 Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately 

if defective.  

 Use Copper Conductors in Field Wiring Only, 60/75° C 

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous 
locations only 

 

WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been 
switched off or the area is known to be non-hazardous. 
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, 
COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON 
DANGEREUX.

 

 

WARNING:  To avoid the risk of electric shock or burns, always connect the safety (or earth) 
ground before making any other connections.  

 

WARNING:  To reduce the risk of fire, electrical shock, or physical injury it is strongly 
recommended to fuse the voltage measurement inputs.  Be sure to locate fuses as close to the  
source as possible. 

 

WARNING:  Replace fuse with the same type and rating to provide protection against risk of fire 
and shock hazards.   

 

WARNING:  In the event of repeated failure, do not replace the fuse again as a repeated failure 
indicates a defective condition that will not clear by replacing the fuse.  

 

WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for 
Class I, Division 2 
AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT 
RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, 
DIVISION 2  

 

WARNING - The USB parts are for operational maintenance only. Do not leave permanently 
connected unless area is known to be non-hazardous.

  

 

WARNING – EXPLOSION HAZARD - BATTERIES MUST ONLY BE CHANGED IN AN AREA 
KNOWN TO BE NON-HAZARDOUS 
AVERTISSEMENT - RISQUE D'EXPLOSION - AFIN D'EVITER TOUT RISQUE D'EXPLOSION, 
S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX AVANT DE 
CHANGER LA BATTERIE

 

 

WARNING - Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose Of In 
Fire. 

 

WARNING:  Only qualified electrical personnel familiar with the construction and operation of this 
equipment and the hazards involved should install, adjust, operate, or service this equipment.  
Read and understand this manual and other applicable manuals in their entirety before 
proceeding.  Failure to observe this precaution could result in severe bodily injury or loss of life. 

60

20

100

40

80

20

0

10

100

90
80
70
60
50
40
30

Scans

0

1

2

3

4

5

6

0

7

%

C

o

m

p

le

te

 [

  

  

 ]

Filter
Constant

This device complies with part 15 of the FCC Rules. Operation is subject to the following two 
conditions: 

1.  This device may not cause harmful interference. 
2.  This device must accept any interference received, including interference that may 

cause undesired operation. 

Radiated Emission Compliance: For compliance requirement, a ferrite (Horner P/N FBD006 
supplied with the unit) needs to be placed on the AC/DC line with one loop. 

 

Warning:  Consult 
user documentation. 

Warning:  Electrical 
Shock Hazard. 

No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without 
notice. 

Safety 

 

When found on the product, the following symbols specify: 

 

Summary of Contents for XL6 Series

Page 1: ...urrent Sourcing Pos logic General Specifications Input Ranges Safe input voltage range Input Impedance Clamped 0 5 VDC to 12 VDC 0 10 VDC 0 20 mA 4 20 mA 0 5 V to 12V Current Mode 100 Ω Voltage Mode 500 k Ω Required Power Steady State 500 mA 24 VDC Required Power Inrush 30 A for 1 ms 24 VDC DC Switched 2 5 A for 4 ms 24 VDC AC Switched Nominal Resolution AI full scale Max Over Current 10 Bits 32 0...

Page 2: ... mounting clips provided with the OCS until the gasket material forms a tight seal 5 Connect cables as needed such as communications programming power and CsCAN cables to the ports using the provided connectors 6 Begin configuration procedures 3 Panel Cut Out and Dimensions Note Max panel thickness 5 mm Refer to the XL6 User Manual MAN0883 for panel box information and a handy checklist of require...

Page 3: ...e back cover I O Jumpers I O Jumpers JP are located internally To access remove I O cover of unit Wiring Connectors J1 J2 J3 J4 and I O Jumpers JP1 and JP3 are described in the Wiring and Jumpers section of this document Memory Slot Uses Removable Memory for data logging screen captures program loading and recipes Horner Part No HE MC1 Serial Communications MJ1 RS 232 RS 485 Used for Cscape progra...

Page 4: ...sed upon the option that is desired Pin MJ1 Pins MJ2 Pins Signal Direction Signal Direction 8 TXD OUT TXD OUT 7 RXD IN RXD IN 6 0 V Ground 0 V Ground 5 5 60mA OUT 5 60mA OUT 4 RTS OUT TX OUT 3 CTS IN TX OUT 2 RX TX IN OUT RX IN 1 RX TX IN OUT RX IN 1 8 5V 60mA Max MJ2 Half Duplex Mode Pin MJ2 Pins Signal Direction 8 TXD OUT 7 RXD IN 6 0 V Ground 5 5 60mA OUT 4 TX OUT 3 TX OUT 2 TX RX IN OUT 1 TX R...

Page 5: ... Wiring The XL6 can be wired for Positive Logic inputs or Negative Logic inputs Location of I O jumpers JP and wiring connectors J1 J4 Wiring Specifications For I O wiring discrete use the following wire type or equivalent Belden 9918 18 AWG 0 8 mm 2 or larger For shielded Analog I O wiring use the following wire type or equivalent Belden 8441 18 AWG 0 8 mm 2 or larger For CAN wiring use the follo...

Page 6: ...ely if defective Use Copper Conductors in Field Wiring Only 60 75 C This equipment is suitable for use in Class I Division 2 Groups A B C and D or Non hazardous locations only WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTOR L EQUIPMENT COUPER LE COURANT OU S ASSURE...

Reviews: