background image

MAN0886-03-EN 

 

 

         Specifications / Installation

 

__________________________________________________________________________________________________________________________________________________________________ 

4/28/2009 

                                                                       Page 4 of 6                                                                                                                       ECN # 950 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

  

4.2 

External DIP Switch Settings 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

MJ2 Pinouts in Half and Full Duplex Modes 

 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Table - Ports and Functions 

Functions  

Port 1 (MJ1) 

Port 2 (MJ2) 

RS-232 

 

 

 

 

Hardware Handshaking 

 

 

        X 

Programming 

 

 

        X 

Ladder function 
controlled 

 

 

 

 

Serial Downloable 
Protocols 

 

 

 

 

RS 485 Full duplex 

 

 

 

 

RS485 Half duplex 

 

 

        X 

NET1 Port Pin Assignments 

Pin 

Signal 

Signal Description 

Direction 

V- 

CAN Ground 

 

CN_L 

CAN Data Low 

In/Out 

SHLD 

Shield Ground 

 

CN_H 

CAN Data High 

In/Out 

NC 

No Connect 

 

  4.1 

Serial Communications:  

  
 
 

MJ1:  (RS-232 / RS-485) Use for Cscape programming 

 

and Application-Defined Communications. 

 
 

MJ2:  (RS-232 / RS-485) Use for Application-Defined 

 

Communications.  

As seen when looking at the side of the XL6 unit :   

 
The  DIP  Switches  are  used  for 
termination  of  the  RS-485  ports.  The 
XL6 is shipped un-terminated.  
 
 
To  terminate,  select  one  of  the  DIP 
Switches and configure it based upon 
the option that is desired.  

Pin

 

MJ1 Pins 

MJ2 Pins 

 

Signal 

Direction 

Signal 

Direction 

TXD 

OUT 

TXD 

OUT 

RXD 

IN 

RXD 

IN 

0 V 

Ground 

0 V 

Ground 

5* 

+5 60mA 

OUT 

+5 60mA 

OUT 

RTS 

OUT 

TX- 

OUT 

CTS 

IN 

TX+ 

OUT 

RX- / TX- 

IN / OUT 

RX- 

IN 

RX+ / TX+ 

IN / OUT 

RX+ 

IN 

 

* +5V 60mA Max 

MJ2 Half Duplex Mode 

Pin

 

MJ2 Pins 

 

Signal 

Direction 

TXD 

OUT 

RXD 

IN 

0 V 

Ground 

5* 

+5 60mA 

OUT 

TX- 

OUT 

TX+ 

OUT 

TX-/RX- 

IN/OUT 

TX+/RX+ 

IN/OUT 

 

Pin

 

MJ2 Pins 

 

Signal 

Direction 

TXD 

OUT 

RXD 

IN 

0 V 

Ground 

5* 

+5 60mA 

OUT 

TX- 

OUT 

TX+ 

OUT 

RX- 

IN 

RX+ 

IN 

 

MJ2 Full Duplex Mode 

* +5V 60mA Max 

 
 
 
SW1 -  

ON enables MJ2 RS485 port termination (121 Ohms).  

 

OFF disables MJ2 RS485 port termination. 

 
SW2 & SW3 - ON places MJ2 RS485 port in half-duplex mode.  
 

     OFF places MJ2 RS485 port in full-duplex mode. 

 
SW4 -  

ON enables MJ1 RS485 port termination (121 Ohms).  

 

OFF disables MJ1 RS485 port termination. 

 

 

MJ1 

 

MJ2 

On 

 

Off 

On 

 

Off 

On 

 

Off 

CAN Connector 

 

Use the CAN Connector when using CsCAN network. 

 

Torque rating 4.5 – 7 Lb-In 

(0.50 – 0.78 N-m) 

 
 

Speeds 

10 BaseT Ethernet (10-Mbps) 

100 BaseTx Fast Ethernet (100-Mbps) 

Modes 

Half or Full Duplex 

Auto-Negotiation 

Both 10/100-Mbps and Half/Full Duplex 

Connector Type 

Shielded RJ-45 

Cable Type 
(Recommended) 

CAT5 (or better) UTP 

Port 

Auto MDI/MDI-X 

 

4.3 

CAN Network Port and Wiring 

 

4.4 

Ethernet Port 

 
 

Summary of Contents for XL6 Series

Page 1: ...urrent Sourcing Pos logic General Specifications Input Ranges Safe input voltage range Input Impedance Clamped 0 5 VDC to 12 VDC 0 10 VDC 0 20 mA 4 20 mA 0 5 V to 12V Current Mode 100 Ω Voltage Mode 500 k Ω Required Power Steady State 500 mA 24 VDC Required Power Inrush 30 A for 1 ms 24 VDC DC Switched 2 5 A for 4 ms 24 VDC AC Switched Nominal Resolution AI full scale Max Over Current 10 Bits 32 0...

Page 2: ... mounting clips provided with the OCS until the gasket material forms a tight seal 5 Connect cables as needed such as communications programming power and CsCAN cables to the ports using the provided connectors 6 Begin configuration procedures 3 Panel Cut Out and Dimensions Note Max panel thickness 5 mm Refer to the XL6 User Manual MAN0883 for panel box information and a handy checklist of require...

Page 3: ...e back cover I O Jumpers I O Jumpers JP are located internally To access remove I O cover of unit Wiring Connectors J1 J2 J3 J4 and I O Jumpers JP1 and JP3 are described in the Wiring and Jumpers section of this document Memory Slot Uses Removable Memory for data logging screen captures program loading and recipes Horner Part No HE MC1 Serial Communications MJ1 RS 232 RS 485 Used for Cscape progra...

Page 4: ...sed upon the option that is desired Pin MJ1 Pins MJ2 Pins Signal Direction Signal Direction 8 TXD OUT TXD OUT 7 RXD IN RXD IN 6 0 V Ground 0 V Ground 5 5 60mA OUT 5 60mA OUT 4 RTS OUT TX OUT 3 CTS IN TX OUT 2 RX TX IN OUT RX IN 1 RX TX IN OUT RX IN 1 8 5V 60mA Max MJ2 Half Duplex Mode Pin MJ2 Pins Signal Direction 8 TXD OUT 7 RXD IN 6 0 V Ground 5 5 60mA OUT 4 TX OUT 3 TX OUT 2 TX RX IN OUT 1 TX R...

Page 5: ... Wiring The XL6 can be wired for Positive Logic inputs or Negative Logic inputs Location of I O jumpers JP and wiring connectors J1 J4 Wiring Specifications For I O wiring discrete use the following wire type or equivalent Belden 9918 18 AWG 0 8 mm 2 or larger For shielded Analog I O wiring use the following wire type or equivalent Belden 8441 18 AWG 0 8 mm 2 or larger For CAN wiring use the follo...

Page 6: ...ely if defective Use Copper Conductors in Field Wiring Only 60 75 C This equipment is suitable for use in Class I Division 2 Groups A B C and D or Non hazardous locations only WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTOR L EQUIPMENT COUPER LE COURANT OU S ASSURE...

Reviews: