APPENDIX A 12-5-97 PAGE 34
Data Formats
The Drive Parameters listed in the previous pages describe the "format" in which the data is presented.
There are 17 different formats, all listed in this manual section. For further details beyond this manual,
consult the user documentation provided with the drive.
FORM AT 0
Direct Translation
FORMAT 1
READ
WRITE
/10
X10
FO R M AT 2
R E AD
W R ITE
/10 0
X 10 0
Fault Codes
Code
Type
Description
Code
Type
Description
0
-
No Trip History
12
OH3
Overheat (Internal Temp.)
1
OC1
Overcurrent During Acc.
13
OH2
External Fault
2
OC2
Overcurrent During Dec.
14
dbH
DB Resistor Overload
3
OC3
Overcurrent Steady State Running
15
FUS
DC Fuse Burnout
4
EF
Ground Fault
16
Er1
Memory Error
5
OV1
Overvoltage During Acc.
17
Er3
Inverter CPU Error
6
OV2
Overvoltage During Dec.
18
Er4
Option COmmunications Error
7
OV3
Overvoltage Steady State Running
19
Er5
Option Malfunction
8
LV
Low Voltage
20
Er6
Keypad Panel Operation Error
9
OL
Electric Thermal Overload Relay
21
Er7
Auto Tuning Error
10
OLU
Inverter Overload
22
Er2
Keypad Panel Communication Error
11
OH1
Heatsink Overheat
Format 3
LOW WORD
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
PRIOR FAULT #1
0
0
0
PRESENT FAULT
HIGH WORD
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
0
0
0
PRIOR FAULT #3
0
0
0
PRIOR FAULT #2