HORNE T105A Installation, Operating And Maintenance Instructions Download Page 8

Horne Engineering Ltd 

Issue 7, November 2018 

 

 

 

 

8

 

To remove the spray plates from the fixed shower head, rotate the lock rings to 30 degrees anticlockwise 
to release the bayonet fitting and then ease out the spray plates by the lock ring.  Note that for the fixed 
showerhead, a tool is supplied with the showerhead to engage the lock ring as shown in Fig 10.  
 

 

 
Fig 10. 
 
See attached drawings 8341 and 8342 for parts lists for ordering spares. 
 

IN-SERVICE TESTING 

 

Periodic testing should be carried out to check whether or not any deterioration has occurred in the 
performance of the TSV1-3. The results of these tests, and the equipment used, should be recorded on 
the Commissioning, Maintenance and In-Service Testing Sheet at the back of these instructions. Fill in all 
the parameters requested on the sheet.  
 
Note that instrumentation to the same specification should be used each time when measurements are 
taken to ensure consistency of results. Record all the information on the In-Service Testing sheet at the 
back of these instructions. 
 
A thermal shut-

off test, as described under “Maintenance” above, should be carried out.  Ensure that the 

servicing valves are fully opened (see Fig 6) before performing this test. If mixed water continues to flow 
and is coming from the showerhead at a temperature of more than 2°C above the maximum mixed water 
temperature setting then the TSV1-3 is due for maintenance. Any requirement to adjust the Mixed Water 
Temperature should be recorded, and the strainers checked for cleanliness, and check valves checked. 
 

Note: A thermostatic mixing valve in need of maintenance can be undetectable in normal use and 
only become apparent when disruption occurs in the hot or cold water supply temperatures or 
pressures. In service testing should be carried out at a frequency to detect any such deterioration. 

 
The frequency of in-service testing depends upon the condition of the water passing through the TSV1-3.  
In-service testing must be carried out more frequently in hard water areas than in soft water areas.  As a 
general guide, in-service testing should be carried out at intervals somewhere between 6 months and 12 
months.  In-service testing should be carried out at least every 12 months and, where the water is hard, 
the interval may be less than 6 months.  Experience of local conditions and the in-service testing record 
will dictate the frequency of in-service testing. In the absence of practical experience of this, a first check  

– 8 weeks after commissioning should be performed. If no problems are detected (and mixed water temp 

Summary of Contents for T105A

Page 1: ...fed by supplies with differing pressures use the following to determine whether a pressure reducing valve PRV is required on the side with the higher pressure Note that output flow rate is always det...

Page 2: ...head shown p13 Bottom of panel should be 1 1 metres from finished floor level 1 Position the Pre Plumbed Enclosure Identify a suitable position for the Enclosure and mark a line on the wall level wit...

Page 3: ...screw and being careful not to scratch the enclosure or its covers lay it down where it will not be damaged Drill the 4 holes and install the wall plugs 6 Attach the Pre Plumbed Enclosure to the Wall...

Page 4: ...rk in accordance with Water Bylaws 2000 Scotland and BS 6700 1997 England Wales The use of a Horne flushing kit is strongly recommended because this connects directly to the water inlets to the mixing...

Page 5: ...before the pre plumbed enclosure is attached to the wall Accordingly point 7 on the attached installation instructions Connect the Supply Pipes should be performed before point 6 Attach the Pre Plumbe...

Page 6: ...ve the set temperature In either case there is no scalding risk If the temperature rises above this then it is likely that there is contamination in the TSV1 3 that is preventing it from shutting off...

Page 7: ...2 5 Nm Ensure the on off assembly is torqued down to 25 Nm 34 lbft to prevent the user from inadvertently unscrewing the assembly during flow control Do not over tighten the assembly The Check Valves...

Page 8: ...efore performing this test If mixed water continues to flow and is coming from the showerhead at a temperature of more than 2 C above the maximum mixed water temperature setting then the TSV1 3 is due...

Page 9: ...fter commissioning If small adjustments 1 to 2 K are required then check the strainers for cleanliness make sure the isolating valves are fully open and verify the check valves are operating correctly...

Page 10: ...Horne Engineering Ltd Issue 7 November 2018 10...

Page 11: ...Horne Engineering Ltd Issue 7 November 2018 11...

Page 12: ...Horne Engineering Ltd Issue 7 November 2018 12...

Page 13: ...Horne Engineering Ltd Issue 7 November 2018 13...

Page 14: ...Max Mixed Water Temp during CW Isolation test C Mixed Water Temp on restoration of CW Supply C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments...

Page 15: ...y C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments Recommended Date of Next In Service Test In Service Testing Record Establishment Location of...

Page 16: ...ng Ltd Issue 7 November 2018 16 Brochure Ref L 189 T10XA Horne Engineering Ltd PO Box 7 Rankine Street Johnstone SCOTLAND PA5 8BD Tel 44 0 1505 321455 Fax 44 0 1505 336287 Email Technical horne co uk...

Reviews: