background image

Page 10

24VF Gas Fireplace

Part No. XG0138

Horizon 

Maintenance

Gas Control Valve

Figure 11. 

SIT NOVA 630.570 for LP

.

Pilot  Burner Adjustment

1.

  Locate Pilot Adjustment Screw. 

(See figure 11.)

2.

  Adjust pilot screw to provide properly sized flame as shown in

 

 figure 12).

3.

  After installing or servicing, leak test with a soap solution with 

main burner on. Coat pipe and tubing joints, gasket etc. with soap 

solution. Bubbles indicate leaks. Tighten any areas where the 

bubbles appear until the bubbling stops completely.

Figure 12. 

Pilot Burner

WARNING:

Do not use a blower insert or heat exchanger insert, it is 

not approved for use with this fireplace.

 Avoid any drafts 

that alter burner flame patterns. 
Do not use accessories not approved for use with this heater.

Cleaning the Oxygen  

Depletion Sensor (ODS)

The most common problem with the vent-free fireplace is a dirty 

ODS.The symptoms of a dirty ODS can be any of the following:

A.  Pilot will not stay lit.
B.  Stove runs for a little while and goes out completely, including 

pilot.

The cleaning process is a very simple procedure. You will need 

a can of compressed air (as used for cleaning computers). This 

is available at hardware and computer stores, and is sometimes 

labelled as a "duster". Do NOT use an air compressor, as the air 

from a compressor usually contains oil. The correct product usu

-

ally has a small straw that connects to the can to aim the air.

  Cleaning the ODS Sensor 

 

(Must be performed by a certified gas technician):

1.  Locate the pilot assembly on your stove.
2.  Turn on the gas valve on the stove to the off position and let the 

stove cool down.

3.  Locate the ODS intake hole (as shown below) and blow the hole 

out. Use several blasts of the air to get all the dust. (Note: the as

-

sembly shown below is an LP assembly. The natural gas version 

has some minor differences)

4.  Your stove should now operate normally.
5.  If it does not, in some extreme cases, the ODS can be so clogged 

that it is necessary to disconnect the gas supply leading to the 

pilot tube. You must use one 7/16" wrench to hold the ODS and 

another to remove the nut. (see below) Blow into the tube from 

the nut end. If you are required to do this, you must leak test the 

nut after reconnecting by using a 50/50 solution of dish soap and 

water around the nut area. If you see bubbles when holding the 

pilot button depressed, tighten the nut.

6. 

NEVER insert any objects into either the flame hole or intake 

hole. 

The ODS is a precision instrument and if damaged, will not 

Summary of Contents for 24VF

Page 1: ...ire or explosion may result causing propertydamage personalinjury or loss of life F o r Y o u r Safety Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combus tion and ventilation air must be provided Refer to page 3...

Page 2: ... are in the same room as the appliance Clothing or other flammable materials should not be placed on or near the appliance Any safety screen or guard removed for servicing an ap pliance must be replaced prior to operating the heater Installationandrepairshouldbedonebyaqualifiedservice person The appliance should be inspected before use and at least annually by a professional service person Morefre...

Page 3: ... barrier This will reduce the possibility of a cold air convection current on the fireplace Space Requirements This heater must not be installed in a confined space or unusually tight construction unless provisions are made for adequate combus tion and ventilation air The National Fuel Gas Code ANSI Z223 1 defines a confined space as a space whose volume is less than 50 cubic feet per 1 000 BTU pe...

Page 4: ...valve pressure measuring port If leaks are determined then repair and repeat the pressure test procedure 5 Turn main gas control pilot knob OFF during any pressure testing Test pressure should be equal to or less than 3 5 kPa to prevent dam age to control valve 6 Installation requirements and combustion and ventilation air provi sions must conform with local codes 7 Keep the operating area clear a...

Page 5: ...Y WAY to do so restricts the air supply for the control compartments and it also prevents access for servic ing controls The face of the fireplace may be painted to match the room decor provided you use a heat resistant paint Decorative facing must not extend past the fireplace opening at all because it will interfere with the access to retainers for removal of screen door Figure 6 Combustible man...

Page 6: ...lling the Logset Installing the Logs The 24VF is supplied with a two piece fibre logset The logset is very fragile and must be handled very carefully 1 Remove the screen door as shown in figure 8a 2 To install the logs place the rear log in place on the rear log rest Ensure that the log is centered in place as shown below Place the front log in place on the front logrest and center it in place 3 R...

Page 7: ...m then the room is an unconfined space and qualifies for unvented heater installation If the result is less than the accumulated BTU of all the appliances in the room then the room is a confined space and the unvented heater should not be installed in such a small room This heater shall not be installed in a room with unusually tight construction as defined as follows Walls and ceilings exposed to...

Page 8: ... supplier call the Fire De To Turn Off Gas To Appliance Operating Instructions 1 Flip down the lower grill 2 Push in gas control knob slightly and turn clockwise to Off Do not force 3 Flip up the lower grill 1 STOP Read the safety information above on this label 2 Flip down the lower grill 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas...

Page 9: ...ce if any part has been under water Imme diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions Lighting Instructions See page 8 Burner Adjustment The 24VF is equipped with an adjustable burner allowing you to raise or lower the flames 1 Light the pilot as per the light...

Page 10: ...rs This is available at hardware and computer stores and is sometimes labelled as a duster Do NOT use an air compressor as the air from a compressor usually contains oil The correct product usu ally has a small straw that connects to the can to aim the air Cleaning the ODS Sensor Must be performed by a certified gas technician 1 Locate the pilot assembly on your stove 2 Turn on the gas valve on th...

Page 11: ...ce these parts CORRECTIVE ACTION Push the knob in at PILOT position and spark piezo ignitor for at least 10 seconds If pilot does not light repeat 2 or 3 more times If pilot still does not light call a certified technician Bleed air from line eliminate draft make sure gas is going to pilot Ventilate room and let stove burn for a while Ventilate room and stop using odor causing products while stove...

Page 12: ...Page 12 24VF Gas Fireplace Part No XG0138 Horizon Notes ...

Page 13: ...manufactured or supplied by Montigo DelRay Corp 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and unde...

Page 14: ...Canadian Heating Products 27342 Gloucester Way Langley BC XG0138 122006 Installed and Serviced by Horizon ...

Reviews: