2 Product Specification
Linear actuators MC250 • MC253 • MC500 • MC503
10
Version 2.1 - March 2011
Operating Manual
2.4.8
Autotest
If a valve is not actuated over a long period, the valve cone may seize. The
Autotest function prevents this. If the Autotest function of the linear actuator is
switched on, the linear actuator moves after approx.10 days without actuation
automatically in rapid traverse to the limit position set by coding switch S7 and
returns to the starting position.
5.6 Set Autotest and Autopause
2.4.9
Autopause
The actuator uses this function to count the actuator commands which mean a
change in direction. In the event of more than 20 different directional actuator
commends per minute, a compulsory pause of 3 s is imposed.
5.6 Set Autotest and Autopause
2.4.10
Potential-free way-switch (optional extra)
The optional way-switch printed circuit board
can be used to set two lift
positions at which a potential-free electrical contact is opened or closed.
5.8 Set potential-free way-switch
2.5
Technical data
Type
MC250/24, MC253/24,
MC500/24, MC503/24
MC250/230, MC253/230,
MC500/230, MC503/230
Supply voltage
24 V AC ± 10%
24 V DC ± 10%
115 V AC ± 10%
230 V AC + 6% -10%
Power consumption
max. 18 VA
max. 25 VA
Weight
MCxx0 = 7 kg
MCxx3 = 7,4 kg
MCxx0 = 8,2 kg
MCxx3 = 8,6 kg
Dimensions
See Technical Datasheets
Stroke
max. 2.36 in
max. 2.36 in
Frequency
50/60 Hz ± 5%
50/60 Hz ± 5%
Ambient temperature
-10 to +140.00°F
-10 to +140.00°F
Enclosure protection
IP 54
IP 54
Operating mode
S3-50% ED
S3-50% ED
Set time
2,5 bzw. 5 s/mm
2,5 bzw. 5 s/mm
Actuating power
MC25x = 2,5 kN
MC50x = 5 kN
The specified actuating
power is only achieved in
operation at 24 V DC with
rectified AC voltage.
MC25x = 2,5 kN
MC50x = 5 kN
Table 1
Technical data