5 Commissioning
Linear actuators MC250 • MC253 • MC500 • MC503
Operating Manual
Version 2.1 - March 2011
23
5.2
Set input signal
Further information:
5.3
Set actuating time
Further information:
Switch on
off
S1
Ready for operation
-
S2
X characteristic
curve
X characteristic
curve
S3
Y characteristic
curve
Y characteristic
curve
S4
Input signal (Y)
0 … 10 V DC or 0 … 20 mA
Input signal (Y)
2 … 10 V DC or 4 … 20 mA
S5
Actuating time 2.5 s/mm
Actuating time 5 s/mm
S6
Autotest and Autopause on
Autotest and Autopause off
S7
Limit position for actuator spindle
extended
Limit position for actuator spindle
retracted
S8, S9
The hysteresis (0.05 … 0.5 V) is set using S8 and S9.
S10
Input signal (Y) in mA
Input signal (Y) in V
Table 4
Coding switch positions
Stroke
X
Stroke
X
Stroke
Y
Stroke
Y
Diagram 16
Set input signal
0 ... 10 V
0 ... 20 mA
mA
2 ... 10 V
4 ... 20 mA
V
Diagram 17
Set actuating time
2.5 s/mm
5 s/mm