Installation
Manual_Grid_Power_FNC_en_V3_0
31
8.2.3.
Connecting the Battery System
Connect the grid|power FNC
®
cells electrically after you have placed them to a rack or
cabinet. Use only original HOPPECKE accessories.
Several grid|power FNC
®
cells can form a row. One or more rows form the battery system.
1. The contacts must be clean and free from any traces of corrosion.
2. Connect the grid|power FNC
®
cells to each other to form a row.
1 = screw
2 = spring washer
3 = connector
4 = terminal
Note
Use spring washers.
Spring washers ensure a permanent and secure fit of the connectors on the terminal posts.
Torque:
M8 = 20 Nm ± 1 Nm
M10 = 25 Nm ± 1 Nm
3. Install isolation rails to the connectors.
Note
The isolation rails are available as a yard good, also in flame retardant material according to
UL94-V0. They can be used for 3 mm and for 6 mm standard connectors.