Installation
Manual_Grid_Power_FNC_en_V3_0
32
4. Connect the rows to each other.
ATTENTION!
Risk of damage to the battery system.
The cross section of the row connectors must match to the current strength.
Row or end connector:
1 = cover cap
2 = screw
3 = spring washer
4 = cable with cable eye
5 = terminal
Row or end connector with connection
bracket:
1 = cable with cable eye
2 = nut
3 = spring washer
4 = screw
5 = washer
6 = terminal
7 = connection bracket
8 = spring washer
9 = screw
Note
Ensure that the wiring of the row and end connectors is proof against short-circuits:
Use wiring material with at least 3 kV dielectric strength.
Let a distance in air of at least 10 mm between the wiring and electrically conductive parts.
Alternatively, additional insulation may be used.
Any mechanical loading of the end terminals is to be avoided by the fixing of the row and end
connectors.
Avoid any mechanical load on the terminals with connecting the row and end connectors.
Use only original HOPPECKE accessories.