Honeywell Process Solutions
Wireless Dual Analog Input Interface Transmitter
20
User Manual
Rev. 8
July 2012
Figure 5.3: Menu Map to RF ID Setting
Once you have selected the RF ID you wish to use for this particular
Transmitter, exit the menus and return to the Operations Sequence.
The Transmitter should now be successfully configured to the Base Radio.
To check this, press ENTER while the Transmitter is in the Operations
Sequence for the Read-Only Sequence to be displayed. You may see an
RF SYNC message displayed on the Transmitter LCD. This means that
the Transmitter and Base Radio are attempting to synchronize communica-
tions. If this is successful, the RF Status will display an RF OK message.
If this is unsuccessful, the RF Status will display a NO RF message.
Also notice the two small arrows on either side of the LCD; if they are
fluctuating up and down, that indicates the Transmitter and Base Radio are
successfully communicating. If only one or none of the arrows are moving
then they are not communicating successfully.