XNX Universal Transmitter
Installation and Operation
79
mA Levels
This option allows the user to select mA output levels for inhibit,
fault, and overrange. Beam block and low signal apply to
Searchline (see the table in the next column).
Figure 100. mA Levels menu
Using the
switches, move to the mA output to be changed
and use
✓
to select it.
✓
Figure 101. Set mA Levels for Warning screens
Use the
switches to decrease or increase the value until the
desired value appears. Use
✓
to select the value and move to the
next setting. Repeat for each setting to be changed.
The default values and available output ranges for Inhibit,
Warning, Overrange, Beam Blocked, and Low Signal are shown in
the following table. See
for more information.
Signal
Output (mA)
Default
Min
Max
I
Inhibit
2.0
1.0
3.5
W
Warning
3.0
1.0
3.5
O
Overrange
21.0
20
22
B
Beam Blocked
1.0
1.0
4.0
L
Low Signal
1.0
1.0
4.0
Figure 102. Set mA Levels for Inhibit screen
After all changes have been made, use the switches to
move to the ‘
ü
’ and use
✓
on the front panel to accept and
save the settings. If
‘
ü
’ is not selected, none of the changes will
be saved.
Figure 103. mA Settings Saved screen
Calibration Interval
Calibration Interval allows a desired interval for sensor
calibration to be set for sensors attached to the transmitter. The
transmitter will generate a warning when the interval is reached.
Figure 104. Calibration Interval menu
Calibration Interval will not appear when an IR personality board
is attached and the mA sensor type is set as ‘Other mA Sensor’.
Summary of Contents for XNX-AM Series
Page 2: ...This page is intentionally left blank ...
Page 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Page 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Page 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Page 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Page 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Page 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Page 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Page 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Page 177: ...XNX Universal Transmitter Control Drawings 175 ...
Page 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Page 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Page 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Page 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...