XNX Universal Transmitter
Warnings/Faults
127
Fault
Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data
Action For Resolution
F112
Sensor 24 VDC
Supply Bad
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check the wire of the 24V power supply to the transmitter and the power
supply operation. Also check the wiring between the transmitter and the
Optima/Excel.
F113
Sensor Internal
5V Power Supply
Defect
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Remove and return to Honeywell for repair.
F114
Sensor Internal
Lamp Issue
Optima
Latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Remove and return to Honeywell for repair.
F116
Sensor Internal
Failure
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Remove and return to Honeywell for repair.
F117
Sensor Loop
Failure, (Sensor
is losing/has lost
mA output signal.
These are detected
by Optima and
Excel, F161 is de-
tected by XNX and
will usually occur
before F117.)
Optima,
Excel
Latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check that supply voltage is stable. Check wiring between Optima/Excel
and the transmitter. Check loop impedance of wiring. Check that switch-
es S3 and S4 are set correctly. If the switch settings need to be changed,
power down the transmitter before changing the switch settings. Once
the problem has been resolved, a Soft Reset must be performed for the
Calibration menu to clear F117.
F118
Sensor Real Time
Clock issue
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic con-
trolled by sensor
Sensor fault or warn-
ing code (Note 4)
Reset “date and time” in Excel, recycle Excel power, and confirm “date
and time. If not retained, remove and return to Honeywell for repair.
Summary of Contents for XNX-AM Series
Page 2: ...This page is intentionally left blank ...
Page 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Page 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Page 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Page 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Page 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Page 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Page 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Page 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Page 177: ...XNX Universal Transmitter Control Drawings 175 ...
Page 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Page 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Page 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Page 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...