XLS-REL trouble indications
4.2
XLS-REL Technical Reference Manual
XLS-REL indications on XLS100 panels
Warning!
Disconnect all wiring on TB4 of the XLS-REL
(release circuits 1 and 2) during system service. Disabled points
will not prevent activation of the release circuits. Failure to
follow these instructions may result in loss of life, serious injury,
or property damage.
After the successful completion of the programming process, the
fire alarm control panel will reset itself. Upon reset, device
supervision may cause the panel to generate a Dev/Line fault for
each XLS-REL circuit. This is a normal indication, and it should
go away within minutes. Table 4-1 lists the indications you may
see for the XLS-REL on the 2-LCD.
Table 4-1: Releasing Module indications
Device
Condition
LED
2-LCD message
Abort
Short
Monitor
None, unless there is another event
Open
Trouble
Open Fault
Abort*
Manual
Short
Alarm
1st Fire Alarm
Manual*
Open
Trouble
Open Fault
Manual*
Prerelease_1
Short
Trouble
Short Fault
Prerelease_1*
Open
Trouble
Open Fault
Prerelease_1*
Prerelease_2
Short
Trouble
Dev/Line Flt
Prerelease_2*
Open
Trouble
Open Fault
Prerelease_2*
Abort
Manual
Prerelease_1
Prerelease_2
Release_1
Release_2
No riser
Trouble
Dev/Line Flt
Device (Abort, Manual, Prerelease_1, Prerelease_2,
Release_1, or Release_2)*
Release_1
Short
Trouble
Short Fault
Release_1*
Open
Trouble
Open Fault
Release_1*