Honeywell W8735ER Installation Instructions Manual Download Page 7

W8735ER WIRELESS OUTDOOR RESET MODULE

7

66-1202—01

WIRELESS OUTDOOR RESET MODULE ALARMS AND 

TROUBLESHOOTING

The W8735ER Wireless Outdoor Reset Module’s enhanced diagnostics provides information alerting of deteriorating boiler 

efficiency or if the system is not running optimally. Outdoor reset-related errors can be displayed on diagnostic tools and displays. 

Errors are also displayed on the Aquastat's 3-digit display. See Table 5 for available Outdoor reset-related error codes.

a

Warnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and maintaining 

boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings may indicate a reset curve setting 

error one or more features is not running optimally, and the Aquastat is reverting to default settings or has stopped running the 

Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.

NOTE: Aquastat alarms reset automatically once the alarm condition has been resolved.  Alarms can also be reset by 

cycling power if the alarm condition is no longer present.

Table 5. Aquastat Outdoor Reset Related Error Codes.

Error 

Code

Cause/Action

EnviraCOM 

Alarm

Err 9

a

Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost, Outdoor 

Reset Module failure, multiple outdoor temperature sensors detected on the bus, or outdoor 

temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.

50, 53, 149

Err 10

a

Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive 

cycles. Check Outdoor Reset curve settings.

150

Err 11

a

DHW Module Sensor failure.

Warning: DHW System failure; communication to DHW Module lost, DHW Module failure, or 

temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.

146, 147, 148

Table 6. EnviraCOM Outdoor Reset Alarms and Troubleshooting.

Alarm Desription

EnviraCOM 

Alarm

Troubleshooting

Duplicate Outdoor Temp Alarm Present

50

Only one outdoor sensor (wired/wireless) is allowed.                                                                                                                                    

Ensure no other outdoor sensors is connected.

Outdoor Temp Sensor Low Battery Alert

156

Replace sensor batteries

Outdoor Sensor Missing/Failure

53

Outdoor sensor failure.  Replace sensor.

Missing Outdoor Temp Sensor

149

Module not bound within 5 minutes of power-up or lost once 

enrolled. Check batteries

Summary of Contents for W8735ER

Page 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Page 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Page 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Page 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Page 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Page 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Page 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Page 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...

Reviews: