Honeywell W8735ER Installation Instructions Manual Download Page 3

W8735ER WIRELESS OUTDOOR RESET MODULE

3

66-1202—01

Sensor Binding

The C7089R Outdoor Sensor must be bound with the 

W8735ER Wireless Outdoor Reset Module in order for 

communication between the two controls to be established.

When the W8735ER Wireless Outdoor Temperature Module 

is powered but 

not

 bound to a sensor, the POWER LED will be 

ON (green) and the CONNECTED LED will be OFF.

1.

Remove the cover from the C7089R to expose the 

CONNECT button.

2.

Press the CONNECT button on the W8735ER until the 

CONNECTED LED flashes green (1 blink/second) after 

approximately five seconds of flashing red. If the sensor 

is not bound within the next 15 minutes the W8735ER 

times out and the CONNECTED LED will turn OFF.

3.

While the CONNECTED LED flashes green on the 

W8735ER, press the CONNECT button on the C7089R 

sensor.

4.

The CONNECTED LED will start to blink fast (4 blinks/

second).

NOTE: If flashing doesn’t speed up to 4 blinks/second, 

the sensor and the W8735ER have not bound. 

Repeat step 4. If binding is not successful during 

a 15 minutes period, the W8735ER will time              

out. Repeat steps 2 through 4. Make sure the 

W8735ER and the sensor are positioned at least 

3 feet apart during the binding process.

5.

Once the flashing rate goes back to 1 blink/second, 

press the CONNECT button on the W8735ER to end 

the binding process.

6.

Once the C7089R sensor and the W8735ER bind, the 

CONNECTED LED on the W8735ER will be ON solid 

(green).

7.

Place sensor cover back on the sensor and return the 

sensor to the bracket. See Fig. 3.

NOTE: Pressing the CONNECT button on either the 

W8735ER or wireless sensor for 15 seconds or 

more will result in the unbinding of the wireless 

sensor and deactivation of the OTC functionality.  

To rebind the sensor to the W8735ER follow 

steps 1-7 in this section.

NOTES:

If the W8735ER is bound to a sensor but the sen-

sor signal is lost, the CONNECTED LED will be 

ON (red).

Once the sensor is bound to the W8735ER and 

the module is connected to the EnviraCOM com-

munication bus as described in the WIRING sec-

tion of this document, hold the sensor where you 

intend to install it and check for the outdoor tem-

perature to be displayed on the combustion con-

trol. If the outdoor temperature is not displayed, 

change the positioning of the sensor.

If the W8735ER is not successfully bound to 

C7089R within five minutes of power up, the 

W8735ER will generate a missing sensor alarm.  

See Table 6 for a complete listing of EnviraCOM 

alarms and trobuleshooting guide.

Summary of Contents for W8735ER

Page 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Page 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Page 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Page 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Page 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Page 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Page 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Page 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...

Reviews: